Aerosol Products

Permit Holder Guideline #1

PERMIT TITLE: Aerosol Products

CODE SECTION: (Virginia Statewide Fire Prevention Code) 5101.2

SCOPE:  The provisions of this chapter and NFPA 30B shall apply to the manufacturing, storage, and display of aerosol products. Manufacturing of aerosol products using hazardous materials shall also comply with Chapter 50

FEE:  Annual $200 Payable to the City of Richmond

PERMIT EXPIRATION: One (1) Year from the date issued

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. Material Safety Data Sheets (MSDS) information for aerosol products display shall be kept on the premises at an approved location.
  2. When an active fire protective (alarm or suppression) system is provided, it is the owner or tenant responsibility to have an annual test performed and keep necessary documentation on-site at all times.
  3. Cartons shall be identified on at least one side with the classification level of the aerosol products.
  4. Solid pile and palletized storage shall be arranged so the maximum travel distance to an aisle is 25 feet.
  5. Rack storage shall be arranged with a minimum aisle width of 8 feet between rows of racks and 8 feet between racks and adjacent solid pile or palletized storage. Where early suppression fast response sprinklers provide automatic sprinkler protection, the minimum aisle width shall be 4 feet.

Download the Permit Application

Special Amusement Buildings

Permit Holder Guideline #2

PERMIT TITLE: Amusement Buildings (Special)

CODE SECTION: (Virginia Statewide Fire Prevention Code) 107.2

SCOPE: A permit is required to operate in A building that is temporary, permanent, or mobile that contains a device or system that conveys passengers or provides a walkway along, around, or over a course in any direction as a form of amusement arranged so that the egress path is not readily apparent due to visual or audio distractions or an intentionally confounded egress path, or is not readily available because of the mode of conveyance through the building or structure.

FEE:  Annual $200 Operational $200 Payable to the City of Richmond

PERMIT EXPIRATION: Event Duration (or Annual for permanent sites).

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. All special amusement buildings shall meet all requirements of assembly occupancies (including staff trained and drilled in emergency procedures).
  2. An approved sign noting the maximum occupancy load as approved by the Building Official shall be posted near the main entrance to the assembly room.
  3. The "Certificate of Occupancy" issued by the Building Official shall be available for review by the FIRE OFFICIALS.
  4. No overcrowding allowed. (Defined as exceeding the approved occupant load or crowding that blocks the means of egress).
  5. Exits shall not be secured from the egress side and shall be kept ready for ease of escape during occupancy.
  6. Fire protection equipment shall be maintained and inspected with a copy of the current inspection reports available on site.
  7. No storage of any kind (temporary or otherwise) is allowed to block exits, exit aisles, or exit discharges. All aisles leading to the exits and from the exits to the public way are to remain unobstructed at all times. Parking shall not obstruct exit discharges.

  1. All exit signs shall be visible and all illuminated exit signs shall be illuminated at all times the building is occupied. All egress lighting shall illuminate when tested.
  2. When the design of egress path is designed to confuse; directional exit marking that becomes apparent in an emergency shall be provided.
  3. All decorative materials shall be either noncombustible or flame-resistant in accordance with both large and small scale flame test of NFPA 701. The interior finish of all structures shall be maintained as approved.

Download the Permit Application

Assembly & Educational Occupancies

Permit Holder Guidelines #3

PERMIT TITLE: Assembly & Educational Occupancies

CODE SECTION: (Virginia Statewide Fire Prevention Code) 107.2

FEE: Annual $200 Operational $200 Payable to the City of Richmond

SCOPE: Requirements and Guidelines for Public Assembly & Educational Facilities. Permits may be required by the FIRE OFFICIAL as permitted under the SFPC in accordance with Table 107.2, except that the FIRE OFFICIAL shall require permits for the manufacturing, storage, handling, use, and sale of explosives. In accordance with Section 5601.2.3.1, an application for a permit to manufacture, store, handle, use, or sell explosives shall only be made by a designated individual.

PERMIT EXPIRATION: ONE (1) year from the date issued, unless operational.

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. An approved sign noting the maximum occupancy load as approved by the Building Official shall be posted near the main entrance to the assembly room. The “Certificate of Occupancy” issued by the Building Official shall be available for review by the FIRE OFFICIALS.
  2. No overcrowding allowed. (Defined as exceeding the approved occupant load or crowding that blocks the means of egress.)
  3. A tracking system (hand counters or another method) that correctly reflects the number of people on the premises is to be maintained at all times.
  4. Exits shall not be secured from the egress side and must be kept ready for ease of escape when occupied.
  5. No storage of any kind (temporary or otherwise) is allowed to block exits, exit aisles, or exit discharges. All aisles leading to the exits and from the exits to the public way are to remain unobstructed at all times. Parking shall not obstruct exit discharges.
  6. All exit signs shall be visible and all illuminated exit signs shall be illuminated at all times the building is occupied. All egress lighting shall illuminate when tested.
  7. All decorative materials shall be either non-combustible or flame-resistant in accordance with both large and small scale flame test of NFPA 701. The interior finish of all structures shall be maintained as approved.

  1. No open flame such as candles shall be used without first obtaining approval and a permit from the Fire Marshal’s office.
  2. Fireworks and Pyrotechnics shall not be used without first obtaining approval and a permit from the Fire Marshal’s office.
  3. All employees shall be trained on emergency evacuation procedures and fire extinguisher use and shall participate in quarterly evacuation drills.
  4. All smoking materials shall be disposed of properly to prevent fires.

Download the Permit Application

 

Aviation Facilities, Aircraft Servicing, Repairs, or Fueling from Vehicles

Permit Holder Guideline #4

PERMIT TITLE: Aviation Facilities

CODE SECTION: Statewide Fire Prevention Code) 2001.3

FEE:  Annual $200 Payable to the City of Richmond

SCOPE: An operational permit is required to use a Group H or Group S occupancy for aircraft servicing or repair and aircraft fuel-servicing vehicles. Additional permits required by other sections of this code include, but are not limited to, hot work, hazardous materials, and flammable or combustible finishes.
(Need other permits to do hot work, or store fuel beyond aircraft or vehicle)

PERMIT EXPIRATION: ONE (1) year from the date issued.

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code, any special instructions noted on the permit, as well as the following:

  1. Limit activities to approved areas (per building code and fire code official's inspection).
  2. "No Smoking, Open Flame or Ignition Sources" (including matches or lighters) shall be posted within 50 feet of aircraft fueling/refueling areas.
  3. Activities in the area affected by a fuel spill shall be restricted to the mitigation of that spill until the hazard is removed or mitigated. Promptly report all spills to the Fire Marshal’s office.
  4. Periodically inspect fueling hose (daily, monthly); immediately make safe when faults are found.
  5. Aircraft-fueling vehicles shall be attended and operated only by qualified persons. During fuel-transfer operations; a second qualified person shall participate.
  6. At least (1) 80 B: C rated fire extinguisher readily available during an activity at long-term helipad area. Aircraft fuel-servicing vehicles shall have at least two 20 B: C rated fire extinguishers, with one readily accessible from either side. Number and rating (agent capacity) of fire extinguishers at stationary fuel-dispensing stations are based upon fueling system capacity.
  7. Aircraft operation area and related areas shall be kept free of combustible debris at all times.
  8. Copy of permit, MSDS for fuels, and emergency contact information shall be readily available on-site at all times.

Download the Permit Application

Battery Systems

PERMIT TITLE: Battery System

CODE SECTION: (Virginia Statewide Fire Prevention Code) 601.2

FEE: Annual $200 Payable to the City of Richmond

SCOPE: Permits shall be obtained for refrigeration systems, battery systems, and solar photovoltaic power systems as outlined in Section 107.2. Stationary lead-acid battery system with over 50 gallons of liquid capacity

PERMIT EXPIRATION: ONE (1) year from the date issued.

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. Vented (flooded) batteries shall be provided with safety venting caps and approved methods and materials to control and neutralize an electrolyte spill.

  1. Valve-regulated battery systems shall have self-sealing flame-arresting safety vents and:
    1. approved method and materials for neutralizing an electrolyte leak

    1. a listed device or other approved method to preclude, detect and control thermal runaway

    1. where batteries are inside a cabinet, the cabinet shall:

      1. be vented to avoid more than 1% (by volume of the cabinet) of hydrogen concentration

      1. be within 10 feet of equipment they support when in occupied work areas

      1. have exterior label about the voltage and current of the contained battery system

      1. interior signs about relevant electrical, chemical, and fire hazards.

        3.  Both battery systems shall have approved signs on doors into rooms or buildings containing a stationary lead-acid battery system. The signs shall state that the               room contains a lead-acid battery system, energized electrical circuits and that the battery electrolyte solutions are corrosive are corrosive liquids.

Download the Permit Application

          

Cellulose Nitrate Film

Permit Holder Guideline #6

PERMIT TITLE: Cellulose Nitrate Film

CODE SECTION: (Virginia Statewide Fire Prevention Code) 107.2 & 306

FEE:  Annual $200 Payable to the City of Richmond

SCOPE: A permit is required for the storage, use, or to handle of Cellulose Nitrate Film. Storage of cellulose nitrate film shall be in accordance with NFPA 40.

PERMIT EXPIRATION: One (1) Year from Date of Issue.

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code, NFPA 40, and any special instructions noted on permit, as well as the following:

  1. Nitrate films shall be kept in closed, individual metal cans, or DOT-approved containers; unless being worked on, used, or examined.
  2. Cellulose nitrate film shall not be handled unless the room has at least two remote exits with aisles at least 30 inches wide.
  3. Not more than 15 people shall work in any room at one time where nitrate film is handled.
  4. Tables and racks where nitrate film is stored or worked on shall be made of noncombustible materials or wood not less than one & one-half inch at its smallest dimensions.
  5. In any room where nitrate film is stored or handled; artificial light shall be restricted to incandescent or fluorescent light.
  6. Artificial heat shall be restricted to steam or hot water only and not exceed 15psi. for any room where nitrate film is used or handled.
  7. Cellulose nitrate film shall not used or handled in quantities greater than 50 lbs. unless the room is protected by an Extra Hazard Occupancy Sprinkler System.
  8. Nitrate film not in use shall be stored in an approved cabinet or vault per NFPA 40.
  9. Scrap nitrate film shall be collected daily and stored underwater in a metal container with a tight-fitting cover.
  10. Every room where nitrate film is handled or stored shall be equipped with a water solution or portable water fire extinguisher.

Any nitrate film transported by public conveyance shall comply with DOT shipping regulations and other applicable regulations.

 

Download the Permit Application

Procedures for Dust Explosions Hazards

Permit Holder Guideline #7

PERMIT TITLE: Procedures for Dust Explosion Hazards

CODE SECTION: (Virginia Statewide Fire Prevention Code) 2201.2 & 107.2

FEE: Annual $250.00 Payable to the City of Richmond

SCOPE: Permit required for operations involving combustible dust*.

*Defined: Finely divided solid material which is 420 microns or less in diameter and when dispersed in the air in proper proportions; could be ignited by a flame, spark, or other sources of ignition. Combustible dust will pass through the standard U.S. No. 40 sieve.

*Examples of where dust might be found include Grain elevator, feed mills, or operations in pulverizing aluminum, coal, spices, or similar materials.

PERMIT EXPIRATION: ONE (1) year from the date issued.

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. Smoking or the use of heating or other devices employing an open flame or the use of spark-producing equipment is prohibited in areas where combustible dust is generated, stored, manufactured, processed, or handled.
  2. Accumulation of combustible dust shall be kept to a minimum in the interior of buildings. Accumulated combustible dust shall be collected by vacuum cleaning or other means that will not place combustible dust into suspension in air. Forced air or similar methods shall not be used to remove dust from surfaces.

Download the Permit Application

Combustible Fibers

Permit Holder Guideline #8

PERMIT TITLE: Combustible Fibers

CODE SECTION: (Virginia Statewide Fire Prevention Code) 3107

FEE: Annual $200 Payable to the City of Richmond

SCOPE: Readily ignitable and free-burning materials in a fibrous or shredded form, such as cocoa fiber, cloth, cotton, excelsior, hay, hemp, henequen, istle, jute, kapok, oakum, rags, sisal, Spanish moss, straw, tow, wastepaper, certain synthetic fibers or other like materials. This definition does not include densely packed baled cotton.

PERMIT EXPIRATION: ONE (1) year from the date issued.

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. Ashes, waste, rubbish, or sweepings shall not be placed in wood or other combustible receptacles and shall be removed daily from the structure.
  2. Grass or weeds shall not be allowed to accumulate at any point on the premises.
  3. A minimum clearance of 3 feet (914 mm) shall be maintained between automatic sprinklers and the top of piles.
  4. Loose combustible fibers, not in suitable bales or packages and whether housed or in the open, shall not be stored within 100 feet (30480 mm) of any structure (unless otherwise approved).
  5. Loose combustible fibers in quantities of not more than 100 cubic feet (3m3) located in a structure shall be stored in a metal or metal-lined bin equipped with a self-closing cover.
  6. Loose combustible fibers in quantities exceeding 100 cubic feet (3 m3) are limited to storage areas approved by city building (and/or zoning) code officials. A maximum of 2,500 cubic feet (70 m3) of loose combustible fibers shall be stored in a detached structure, with openings protected against the entrance of sparks. The structure shall not be occupied for any other purpose.

  1. Bailed combustible fibers shall be limited to single blocks or piles not more than 25,000 cubic feet (700 m3) in volume; not including aisles or clearances. Blocks or piles of baled fiber shall be separated from adjacent storage by aisles not less than 5 feet (1524 mm) wide or by flash-fire barriers constructed of continuous sheets of non-combustible material extending from the floor to a minimum height of 1 foot (305 mm) above the highest point of the piles and projecting not less than 1 foot (305 mm) beyond the sides of the piles.
  2. Sisal and other fibers in bales bounded with combustible tie ropes, jute, and other fibers that swell when wet, shall be stored to allow for expansion in any direction without affecting building walls, ceilings, or columns. A minimum clearance of 3 feet (914 mm) shall be required between walls and sides of piles; except that where the storage compartment is not more than 30 feet (9144 mm) wide the minimum clearance at side walls shall be 1 foot (305 mm) provided that a center aisle not less than 5 feet (1524 mm) wide is maintained.

 

Download the Permit Application

Compressed Gases

Permit Holder Guideline #9

PERMIT TITLE: Compressed Gases

CODE SECTION: (Virginia Statewide Fire Prevention Code) 5301.2

FEE: Annual $200 Payable to the City of Richmond

SCOPE: Need a permit for storage, use, and handling of compressed gases, such as any toxic, or over: 200 cubic ft. corrosive or flammable, 504 cubic ft. oxidizing (including oxygen), 6000 cubic ft. inert or asphyxiant, or 12000 cubic ft. air (inclusive of nitrogen or other inert gas with between 16 to 30% oxygen; with less than 16% deemed asphyxiant and over 30% as oxidizer). Partially full containers, cylinders, or tanks containing residual gases shall be considered as full for the controls required. Compressed gas containerscylinders, and tanks shall comply with this section. Compressed gas containerscylinders, or tanks that are not designed for refillable use shall not be refilled after the use of the original contents.

PERMIT EXPIRATION: ONE (1) year from the date issued.

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. Cylinders should be stored in an upright position except for those used in a horizontal position.
  2. Stationary and portable compressed gas containers, cylinders; & tanks shall be marked with the name of the gas and in accordance with NFPA 704. Markings shall be visible from any direction of approach.
  3. Compressed gas containers, cylinders; & tanks shall be secured against accidental dislodgement and access by unauthorized personnel.
  4. Areas used for the storage, use, and handling of compressed gas containers, cylinders, tanks, and systems shall be secured against unauthorized entry and safeguarded in an approved manner.
  5. Compressed gas containers, cylinders, tanks, and systems that could be exposed to physical damage shall be protected. Guard posts or other approved means shall be provided to protect compressed gas containers, cylinders, tanks, and systems indoors and outdoors from vehicular damage.
  6. Compressed gas container, cylinder, and tank valves not being used or serviced shall be protected from physical damage using protective caps, collars, or similar devices.
  7. Compressed gas containers, cylinders, and tanks designed for valve protection caps or other protective devices shall have the caps or devices attached. When outlet caps or plugs are installed, they shall be in place.

Download the Permit Application

Covered Mall Buildings

Permit Holder Guideline #10

PERMIT TITLE: Covered Mall

CODE SECTION: (Virginia Statewide Fire Prevention Code) 403.11.1.1 through 403.11.1.6.

FEE:  Annual 200.00 Operational $40.00 Payable to the City of Richmond

SCOPE: The provisions shall govern the occupancy and maintenance of all structures and premises for precautions against fire and the spread of fire.

Covered Mall Buildings: A single building enclosing several tenants and occupants such as retail stores, drinking and dining establishments, entertainment and amusement facilities, passenger transportation terminals, offices, and other similar uses wherein two or more tenants have a main entrance into a mall area.

PERMIT EXPIRATION: One (1) year from the date issued.

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

Indoor Displays

  1. Fixtures and displays of goods for sale to the public shall be arranged to maintain free, immediate, and unobstructed access to exits.
  2. The display of highly combustible goods, including but not limited to flammable or combustible liquids, liquefied flammable gases, oxidizing materials, pyroxylin plastics, and agricultural goods, in main exit access aisles, corridors, covered malls, or within 5 feet of entrances to exits and exterior exit doors is prohibited when a fire involving such goods would rapidly prevent or obstruct egress.
  3. Liquid or gas-fueled vehicles, boats, or other motor craft shall not be located indoors except as follows:
    1. Batteries are disconnected.
    2. Fuel in fuel tanks does not exceed one-quarter tank (1/4) or 5 gallons (whichever is less).
    3. Fuel tanks and fill opening are closed and sealed to prevent tampering.
    4. Vehicle, boat, or other motor craft equipment are not fueled or defueled within the building.
  4. Storage of combustibles materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur.

  1. Storage shall be maintained 2 feet or more below the ceiling in non-sprinkled areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinkled areas of buildings.
  2. Combustibles materials shall not be stored in exits or exit enclosures.
  3. Combustibles materials shall not be stored in boiler rooms, mechanical rooms, or electrical equipment rooms.
  4. Required emergency evacuation drills shall be held quarterly for all employees to familiarize all occupants with the drill procedure.
  5. Fire safety plans shall include the following:
    1. The procedure for reporting a fire or other emergency.
      1. The life safety strategy and procedures for notifying, relocating, or evacuating occupants.
    2. Site plans indicating the following:
      1. The occupancy assembly point.
      2. The location of fire hydrants.
      3. The normal routes of fire department vehicle access.
    3. Floor plans identifying the locations of the following:
      • Exits.
      • Primary evacuation routes.
      • Secondary evacuation routes.
      • Accessible egress routes.
      • Areas of refuge.
      • Manual fire alarm boxes.
      • Portable fire extinguishers.
      • Occupant use hose stations.
      • Fire alarm annunciators and controls.

    1. A list of major fire hazards associated with the normal use and occupancy of the premises, including maintenance and housekeeping procedures.
    2. Identification and assignment of personnel responsible for maintenance and equipment installed to prevent or control fires.
    3. Identification and assignment of personnel responsible for maintenance, housekeeping, and controlling fuel hazard sources.
  1. A lease plan shall be prepared for each covered mall building. The plan shall include the following information in addition to that required by Fire Safety Plans.

                          Each occupancy, including identification of tenant.

    1. Exits from each tenant space.
    2. Fire protection features, including the following:
      • Fire department connections.
      • Fire command center.
      • Smoke management system controls.
      • Elevators and elevator controls.
      • Hose valves outlets.
      • Sprinkler and standpipe control valves.
      • Automatic fire extinguishing systems areas.
      • Automatic fire detectors zones.
      • Fire barriers.
    3. The lease plan shall be submitted to the fire code official for approval and shall be maintained on-site for immediate reference by responding to fire service personnel.
    4. Unoccupied tenant space shall be kept free from storage, combustible storage waste, and be broom swept clean.
    5. Covered malls buildings exceeding 50,000 square feet shall be provided with a standby power system that is capable of operating the emergency voice/alarm communication.

Download the Permit Application

Permit Holder Guideline #11

PERMIT TITLE: Cryogenic Fluids

CODE SECTION: (Virginia Statewide Fire Prevention Code): 5501.2, 5801.2, 6301.2

FEE: Annual $200.00 Payable to the City of Richmond

SCOPE: Shall obtain a permit to produce, store, use, handle, or dispense cryogenic fluids (boils below -130 F at 14.7 psi) over the amounts listed in Table A below. Permits are not needed for vehicles equipped for and using cryogenic fluids as a fuel for propelling the vehicle or for refrigerating the lading.

PERMIT EXPIRATION: One (1) year from the date issued.

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. Mark containers and post-NFPA 704 sign at the entry to areas with hazardous materials.
  2. Have MSDS and site/floor plan (noting locations of hazardous materials, controls, spill response gear, and items/areas of special concern) readily available on-site and a current copy filed with FIRE OFFICIAL.
  3. Containers, piping, valves, and other appurtenances to be protected from damage and tampering; appropriately marked as to contents and function.
  4. No containers shall be within 10 feet of air intakes, building exits, or combustible materials.
  5. Containers and systems to have pressure release valves, easy for inspection and maintenance.
  6. Promptly remove, replace or repair leaking, damaged, or corroded containers or systems.
  7. Areas with controls or potentially hazardous contact to persons to be adequately lighted.

Table A:

Type

Inside a Building

Outside of Building

Flammable:

More than 1 gallon

60 gallons

Oxidizer (includes oxygen)

10 gallons

50 gallons

Inert

60 gallons

500 gallons

Physical or health hazard,(not indicated above)

Any amount

Any amount

For SI: 1 gallon = 3.785 L

 

Download the Permit Application

Permit Holder Guideline #12

PERMIT TITLE: Dry Cleaning

CODE SECTION: (Virginia Statewide Fire Prevention Code) 2101.2

FEE: Annual $200 Payable to the City of Richmond

SCOPE: The use and storage of solvents used in dry cleaning system operations.

PERMIT EXPIRATION: ONE (1) year from the date issued.

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. Dry cleaning solvents shall be classified according to their flashpoints.
  2. Classification of dry cleaning plants and systems shall be classified based on the solvents used.
  3. Staff shall be trained for equipment or chemical emergencies.
  4. Dry cleaning by immersion and agitation in open vessels are prohibited.
  5. No solvent shall be used with a flashpoint below the machine’s design or listing.
  6. Maximum 1-gallon solvents with a flashpoint below 100 F/ 38 C at each work station; dispensed by approved safety can for spotting and pre-treating.
  7. A minimum of two 2-A:10B: C portable fire extinguishers shall be provided near the doors inside dry cleaning rooms containing Type II, Type III-A, and Type III-B dry cleaning systems.

Download the Permit Application

Permit Holder Guideline #13

PERMIT TITLE: Exhibits and Trade Shows

CODE SECTION: (Virginia Statewide Fire Prevention Code) 107.2

FEE: $150.00 to $250.00 Payable to the City of Richmond

SCOPE: An operational permit is required to operate exhibits and trade shows.

PERMIT EXPIRATION: During the times of the event only (operational).

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. A copy of the certificate of insurance, with a face value of no less than one million dollars showing the City of Richmond as “additional insured as the certificate holder, when the event is being held in a facility outside of its normal use group (non-typical use group of a facility).
  2. When the venue has an approved current Assembly permit; no Exhibit and Trade Shows permits are required (non-typical use group is not included).
  3. An approved sign noting the maximum occupancy load as approved by the Building Official shall be posted near the main entrance to the assembly room. The “Certificate of Occupancy” issued by the Building Official shall be available for review by the Fire Officials.
  4. No overcrowding shall be allowed. (Defined as exceeding the approved occupant load or crowding that blocks the means of egress.)
  5. A tracking system (hand counters or another method) that correctly reflects the number of people on the premises is to be maintained at all times.
  6. Entrance doors in all buildings open to the general public shall not be secured from the egress side during periods that the building is open to the general public.
  7. No storage of any kind (temporary or otherwise) is allowed to block exits, exit aisles, or exit discharges. All aisles leading to the exits and from the exits to the public way are to remain unobstructed at all times. Parking shall not obstruct exit discharges.
  8. All exits signs shall be visible and illuminated at all times the building is occupied. All egress lighting shall work as designed.
  9. All decorative materials shall be either non-combustible or flame-resistant in accordance with both large and small-scale flame test of NFPA 701. The interior finish of all structures shall be maintained as approved.
  10. No open flame (such as candles) shall be used without first obtaining approval and/or permit from the Fire Marshal’s office.

  1. All exhibits or trade shows are required to supply the Fire Marshal’s office a set of floor plans to be approved and signed at least 15 days before the event. All floor plans shall be drawn to scale and include the following information:
    1. Name and date of the event and expected capacity
    2. Number of spaces being used
    3. Dimensions and size of exhibits
    4. Exits
    5. Aisles and aisles widths
    6. Registration Areas
    7. Service Areas
    8. Entrances units (headers, kiosks, turnstiles, etc.) and dimensions
    9. Vehicles (interior vehicle display permit may be required)
    10. Covered exhibits, canopies, tents, enclosed or partially enclosed structures
    11. Cooking devices and demonstrations may require a permit when cooking devices are not protected with an approved hood suppression system.
    12. Stages and Seating Areas
  2. All fire protection systems to include additional life safety equipment. Exit doors shall not be hidden or obstructed at any time.
  3. The use of compressed flammable gases (acetylene, hydrogen, propane, and butane) inside the facility is prohibited (unless approved by the Fire Marshal office) while occupied by the general public.
  4. The use of cutting and welding equipment as part of an exhibit shall require approval and a permit from the Fire Marshal’s office.
  5. All combustible waste shall be stored in non-combustible containers and removed from the premises at least once a day.
  6. The use of any hazardous materials in exhibits requires the approval of the Fire Marshal and a request accompanied by the Material Safety Data Sheets (MSDS) shall be submitted to the Fire Marshal’s office at least 21 days before the event.

    17.  All cooking (as part of the event or supporting the event) shall be governed by the VSFPC and subject to a pre-event inspection by the fire code official.

Download the Permit Application

Permit Holder Guideline #14

PERMIT TITLE: Blasting/Explosives

CODE SECTION: (Virginia Statewide Fire Prevention Code) 5601.2

FEE: Payable to the City of Richmond: $300.00 to store explosives at an approved site from one day to one year $600.00 to blast where damage concerns beyond the site. An additional $50.00 is due during normal work hours for each witnessed blast after the initial event.

SCOPE: Need permit to manufacture, store, handle, sell, or use explosives (See Permit Holder Guideline 21A and 21C for fireworks and special effects)

PERMIT EXPIRATION: Operational Permit can be extended by the Fire Official.

REQUIREMENTS: Apply for a permit at least 10 days before the event. Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code, other applicable regulations, and any special instructions noted on permit, as well as the following:

  1. The person in charge of blasting shall not be under the influence of alcohol or drugs which impair sensory or motor skills, shall be at least 21 years of age, and shall demonstrate knowledge of all safety precautions.
  2. Provide a site plan showing explosive storage, blast area, nearby structures, railroads, and utilities including underground). No use or store explosives within 100 feet of any place of habitation.
  3. Provide Certificate of Insurance listing the City of Richmond as "additional insured" (minimum value of $3 million dollars; with an insurance company licensed in Virginia).
  4. Document from the property owner authorizing and stating the reason for the explosive activity.
  5. Information on explosive materials, how to be used, and expected effects beyond blast area.
  6. Notify this office at least one workday before the event, do not detonate until approved.
  7. Secure storage and blast area from unauthorized personnel, post warning signs, and sound alarm before detonating.
  8. Use appropriate measuring devices and record effects of the blast, provide a copy of blast records to the Fire Marshal’s office within 60 days after the event.

Download the Permit Application

Permit Holder Guideline #15 (A)

PERMIT TITLE: Fireworks (Aerial)

CODE SECTION: (Virginia Statewide Fire Prevention Code) 5608.2.1

SCOPE: Need permit before discharging any fireworks within the City of Richmond

FEE: $250.00 Payable to the City of Richmond

PERMIT EXPIRATION: Duration of event.

REQUIREMENTS: Apply for a permit at least 15 days before the event. All fireworks must be electronically ignited only (no hand firing). The manufacture of fireworks within the city is prohibited. Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code, instructions noted on permit, and the following:

  1. Submit site plan showing fireworks area(s), (note the distance to) structures, roads, woods, parking, and audience area; description (including size) of fireworks, mortars, and ground or special displays. Include expected firing plan and transport vehicle description.
  2. Provide Certificate of Insurance covering the use of fireworks, listing the City of Richmond as "additional insured" (minimum face value of $3 million dollars, with an insurance company licensed in the State of Virginia).
  3. Submit a copy of the contract between the customer (sponsor) and contractor (fireworks company); including time, date, location of the event, authorization from the property owner (if not sponsor), and who will provide the materials and services to satisfy fireworks regulations.
  4. Submit name, contact information, and qualifications of contractor and technician (person responsible for fireworks activity, to be on-site during the event) and a copy of this, with technicians and customers (or agent) original signatures agreeing to comply with all regulations.
  5. Comply with NFPA 1123, 1126, and 1124, including appendix and references.
  6. Fire officials may require demonstration of any fireworks (hours or days before the show, on an approved site with secured safety zone, at expense of customer or contractor). Fire officials may require a meeting of parties on-site, days before the event.
  7. Keep unauthorized personnel safely away from fireworks (no smoking nearby).
  8. For every 100 shells, every 100 square feet of ground effects, or parts thereof, there shall be at least one 2.5 gallons pressurized water extinguisher ready in or near the display area.

  1. Allow fire officials to inspect mortars before loading. Mortars must be stable and in good condition. All aerial shells to be loaded, in individual mortars, at least 1 hour before scheduled discharge time; with wiring and all fireworks preparations completed at least 30 minutes before scheduled discharge time.


*ALL AERIAL SHELLS TO BE ELECTRONICALLY IGNITED (no hand firing).
Maximum of 40 shells per ignition. All to be as listed and described in the application package (see # 1); need fire official approval for changes.

  1. At least one adequate adult security staff shall be required for every 100 feet of "Safety Zone" perimeter that is not secured by approved physical barriers; in place before wiring of fireworks and maintained until area deemed safe afterward.
  2. The contractor and sponsor shall be available to fire official days and at least an hour before the event, to resolve all concerns before the fireworks will be allowed.
  3. At least a 15-minute safety cool-off period after the end of fireworks discharge. Late firings will not be allowed. All fireworks not discharged shall be properly removed from the site and the City within 24 hours after the event (expiration of permit). Fireworks to have approved security until removed. Packaging and transport vehicle is to be labeled per applicable codes.
  4. If any injury or damages, within 1 week, both the contractor and the sponsor (customer) shall submit reports to the fire official, including description, names (and means of contact) of the injured party, estimation of the cause of damage, and for repairs/treatments to resolve the condition, plus how safety will be improved to avoid future similar incidents.
  5. Sites, events, or fireworks of special concern will be subject to additional requirements.
  6. Any cleanup needed, as a result of the pyrotechnic device discharge, shall be the responsibility of the sponsor, agent, contractor, and/or technician.
  7. Chain-fused rack maximums: 3 inch shell or less = 15 mortars, 4 inch shell = 12 mortars, 5-6 inch = 10 mortars, no chain-fused racks for shells over 6 inches.
  8. Separation from the audience shall be 100 feet per inch of the diameter of the largest shell.
  9. All racks shall be perpendicular to the audience.

NOTE: FAILURE TO COMPLY WITH ANY REGULATION WILL BE CONSIDERED DUE CAUSE TO DENY OR REVOKE THE PERMIT OR STOP THE DISCHARGE OF FIREWORKS, AND MAY SUBJECT THE RESPONSIBLE PARTY TO LEGAL ACTION. VIOLATIONS OF THE FIRE CODE ARE CLASS 1 MISDEMEANOR, SUBJECT TO PENALTIES OF UP TO $2500 FOR EACH OFFENCE AND / OR UP TO A YEAR IN JAIL.

Click Here to Download the Signature Page

Download the Permit Application

Permit Holder Guideline #15 (B)

PERMIT TITLE: Fireworks/Pyrotechnics Indoors

CODE SECTION: (Virginia Statewide Fire Prevention Code) 5608.2.2

SCOPE: Pyrotechnics in the performance arts in conjunction with theatrical, musical, or similar productions before a proximate audience, performers, or support personnel.

FEE: $250.00 Payable to the City of Richmond

PERMIT EXPIRATION: During the event only (Operational).

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions will be noted on permit, as well as the following:

  1. The permit holder shall furnish a cue sheet with detonation times and a plot plan showing all locations of devices.
  2. The Fire Marshal's office shall be furnished with a certificate of insurance, with a face value of a minimum of one million dollars showing the City of Richmond as an "additional insured". The certificate holder shall be provided no less than 15 days before the event for validation. The insurance shall cover pyrotechnic operations and the insurance company shall be licensed to do business in the State of Virginia.
  3. Submit name, contact information, qualifications, and certifications of contractor and technician. This person is responsible for the pyrotechnic activity and shall remain on-site during the event. The technician and customer's/agents original signatures are required to ensure the operation will comply with state and local regulations.
  4. The permit is issued upon completion of a live demonstration of each device that will be used during the event. Live demonstrations of the device(s) will be done between 3:00 pm & 4:00 pm unless prearranged at the time of application.
  5. All proximate audience displays shall comply with National Fire Protection Association Standards 1123 and 1126.
  6. All applications for proximate audience displays shall include plans indicating the required clearances for spectators and combustibles, crowd control measures, smoke control measures, and requirements for standby personnel and equipment when required by the fire code official.

  1. Persons in charge of pyrotechnics special effects operations shall be 21 years old, demonstrate knowledge in handling, storage, and use of pyrotechnic special effects materials and devices.
  2. The controller key shall be kept in the possession of the technician, except when firing. A room for storage of all pyrotechnic devices and products shall be provided by the venue with a key to secure the assigned area.
  3. All devices shall be pre-loaded before the show. Recharges may be installed during planned intermissions.
  4. Use only products that are in labeled containers and never exceed the manufacturer’s maximum recommended load.
  5. Any misfires shall be handled in accordance with the manufacturer’s instructions.
  6. A minimum of two off-duty Fire Marshals or more when deemed necessary for life safety issues shall be employed by the promoter/venue for a minimum of four hours each, to monitor the production.
  7. Each pyrotechnic device fired during a performance shall be separated from the audience by at least 15 ft. but not by less than twice the fallout radius of the device.

Click Here to Download the Signature Page

Download the Permit Application

Permit Holder Guideline #15 (C)

PERMIT TITLE: Fireworks/Pyrotechnic Storage

CODE SECTION: (Virginia Statewide Fire Prevention Code) 5601.2

FEE: $200.00 (Check payable to the City of Richmond)

SCOPE: An operational permit is required to display fireworks, including proximate audience displays and pyrotechnic special effects in motion picture, television, theatrical, and group entertainment productions.

PERMIT EXPIRATION: During the times of the event only (operational).

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. The permit holder shall comply with all Federal, State, and City of Richmond guidelines for handling, storage, and use of pyrotechnic special effects materials.
  2. The Fire Marshal's office shall be furnished with a certificate of insurance, with a minimum of one million dollars ($1,000,000) showing the City of Richmond as "additional insured" as the certificate holder. The insurance shall cover pyrotechnic operations and the insurance company shall be licensed to do business in the State of Virginia.
  3. All handling and storage pyrotechnic special effects materials shall comply with the National Fire Protection Association Standards 1123, 1124, and 1126.
  4. All pyrotechnic special effects materials shall be in properly labeled containers to include Material Safety Data Sheets (MSDS) for each device.
  5. Persons in charge of pyrotechnics special effects operations shall be 21 years old, shall demonstrate knowledge of all safety precautions related to the handling, storage, or use of pyrotechnic special effects materials and devices.
  6. All pyrotechnic special effects materials and devices shall be stored in accordance with all state and local regulations promulgated by the Department of the Treasury---Bureau of Alcohol, Tobacco, and Firearms.
  7. No smoking, matches, open flame, or spark-producing devices shall be permitted within 50 feet of a pyrotechnic magazine.
  8. Combustible materials shall not be stored within 50 feet (15m) of a magazine.
  9. Secure storage of more than 5 pounds of low explosive fireworks contents, pyrotechnic, or similar materials in magazine monitored (by an automated system or staff with police powers) to promptly alert city Emergency Communications upon unauthorized opening.

Download the Permit Application

Permit Holder Guideline #17

PERMIT TITLE: Flammable and Combustible Liquids

CODE SECTION: (Virginia Statewide Fire Prevention Code) 3401.4

SCOPE: An operational permit required: 1. To use or operate a pipeline for the transportation within facilities of flammable or combustible liquids. This requirement shall not apply to the offsite transportation in pipelines regulated by the U.S. Department of Transportation (DOT) nor does it apply to piping systems.
 

2. To store, handle or use Class I liquids above 5 gallons (19 L) in a building or excess of 10 gallons (37.9L) outside of a building, except that a permit is not required for the following:

     2.1. The storage or use of Class I liquids in the fuel tank of a motor vehicle, aircraft, motorboat, mobile power plant, or mobile heating plant, unless such storage, in the opinion of the fire official, would cause an unsafe condition.

 

PERMIT EXCEPTIONS: Fuel in tanks connected to and used by a vehicle or oil-burning equipment. (See Guidelines # 18A or #18B for removal or closure of underground/above ground tank.)

FEE: $250.00 Payable to the City of Richmond

PERMIT EXPIRATION: ONE (1) year from the date issued.

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

  1. Submit site plan for exterior storage and building floorplan for interior storage, sample MSDSs with a list of maximum expected quantity of each type of hazardous material, and a brief description of how used and safety provisions (including emergency procedures and fire protection systems).
  2. All containers must be approved for contents, properly labeled, and properly maintained. The proper disposal of empty containers and waste materials shall be documented. Containers and piping subject to damage from vehicular impact shall be adequately protected.
  3. Post signs and maintain NO SMOKING or open flames along with other advisories as need.
  4. Any leaks or spills will be reported immediately to the Fire Department by calling 911.
  5. Appropriate electrical bonding or grounding shall take place during liquid transfer.

  1. No flammable liquids in a basement, keep flammable or combustible liquids more than 3 feet below ceiling and sprinklers. Stay within the limit per control area or occupancy use per the Virginia Statewide Fire Prevention Code. All excess beyond 10 gallons for routine maintenance or operations shall be kept in approved liquid storage cabinets.
  2. Outdoor storage areas will be protected against tampering or trespassers where necessary and remain clear of weeds, debris, and other unneeded combustible materials.
  3. Additional fire code concerns apply if using such liquids for cleaning, dispensing from stationary or mobile tanks, within the piping system, bulk transfer, or additional permits might be required based upon details of operations and other materials.

Download the Permit Application

Permit Holder Guideline #18A

PERMIT TITLE: Above Ground Storage Tank Removal

CODE SECTION: (Virginia Statewide Fire Prevention Code) 5704.2.13.1.4 & 5704.2.14.1

FEE: $45.00 fee for pre-permit inspection if seeking permission to leave the tank or piping in place.
$45.00 for each above ground tank at the location.
$45.00 for any additional visits to re-inspect tank site.

PERMIT EXPIRATION: ONE (1) month from date issued.

REQUIREMENTS: Any tank leaking or not used for more than one year MUST be removed. Tanks may be left in place with the prior approval of the Fire Marshal. Permits are written and issued on-site, as Fire Prevention personnel witness completion of tank removal. If a permit is issued to anyone other than the landowner, the person receiving the permit shall ensure that the landowner receives at least one copy of the said permit. Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on the permit, as well as the following:

  1. Before ANY above ground tank is removed an inspection shall be scheduled through the Richmond Fire Prevention office AND a permit is required before removal.
  2. All flammable liquid storage tanks shall be degassed before removal. The tank shall be cleaned of contents if allowed to remain inside a building or crawl space. All removed tanks are to be disposed of properly. Tank contents to be properly disposed of. Tank contents, tank destination, soil sample, any contaminated soil reports, tank size, tank location, and date of abandonment are to be documented. 
  3. All tank piping shall be removed or emptied of contents and permanently mitigated (i.e. capped or plugged) to ensure there are no remaining hazards.
  4. See Permit Holder Guideline #25 if plans include the use of flame or spark-producing equipment.

The Richmond Fire Marshal’s Office suggests that landowners contact the Virginia Department of Environmental Quality (629 E. Main St., Richmond, VA 23240; phone 804-648-4000 or 800-592-5482, https://www.deq.virginia.gov/) regarding regulations for commercial tanks, leaking tanks, and ground contamination concerns.

Download the Permit Application

 

Permit Holder Guideline #18B

PERMIT TITLE: Underground Storage Tank Closure/Removal

CODE SECTION: Virginia Statewide Fire Prevention Code) 5704.2.13.1.4 & 5704.2.14.1

FEE: $45.00 fee for pre-permit inspection if seeking permission to leave the tank or piping in place.
$200.00 for each tank Payable to the City of Richmond
$45.00 for any additional visits to re-inspect tank site after the first scheduled visit.

SCOPE: Permit required to remove or abandon (including filling in place) an Underground Storage Tank (UST) used for combustible or flammable liquids.

EXCEPTION: For residential heating oil tanks less than 1,000 gallons see addendum.

PERMIT EXPIRATION: ONE (1) month from date issued.

REQUIREMENTS: Any tank not used for more than one year, or with indication of leakage, shall be removed. Tanks may be left in place with the prior approval of the Fire Marshal. Permits are written and issued on site, as Fire Prevention personnel witness completion of tank removal. If a permit is issued to anyone other than the land owner, the person receiving the permit shall ensure that the land owner receives at least one copy of said permit. Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on the permit, as well as the following:

  1. If applicant is seeking permission to abandon a tank in place, a pre-permit inspection shall be scheduled through the Fire Prevention office.
  2. Permit inspections shall be scheduled through the Fire Prevention office for tank removals, filling-in-place, or tank abandonment.
  3. All flammable liquid storage tanks shall be degassed prior to removal or cutting of tank. All removed tanks are to be disposed of properly. Tanks contents to be properly disposed. Destination for tank and liquid contents to be noted when applying for permit.
  4. Tanks which are not removed must be filled with an approved foam or flowable-fill cement. (see addendum). All above ground tank piping shall be removed, with remaining piping permanently capped or plugged below grade to prevent refilling. Record tank size, location and date of abandonment.

ADDENDUM - Abandonment of residential heating oil tanks 1,000 gallons or less:

  1. Owners may request to abandon residential heating oil tanks of 1,000 gallons or less by filling with an approved inert solid. Requests are subject to the approval of the Fire Marshal or his/her designee.

The Richmond Fire Marshal’s Office suggests that landowners contact the Virginia Department of Environmental Quality (629 E. Main St., Richmond, VA 23240; phone 804-648-4000 or 800-592-5482, https://www.deq.virginia.gov/) regarding regulations for commercial tanks, leaking tanks, and ground contamination concerns.

Download the Permit Application

 

Permit Holder Guideline #19

PERMIT TITLE: Floor Finishing

CODE SECTION: (Virginia Statewide Fire Prevention Code) 2410

FEE: $200.00 Payable to the City of Richmond)

SCOPE: An operational permit is required for floor finishing or surfacing operations exceeding 350 square feet (33m) using Class I or Class I liquids).

PERMIT EXPIRATION: Operational

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

  1. Heating ventilation and air-conditioning systems shall not be operated during resurfacing or refinishing operations within 4 hours of the application.
  2. Floor surfacing and finishing operations shall not be conducted while an establishment is open to the public
  3. The power shall be shut down to all electrical sources of ignition within the flammable vapor area
  4. To prevent the accumulation of flammable vapors, mechanical ventilation at a minimum rate of 1 cubic foot per minute per square foot. Vapors shall be exhausted to the exterior of the building by a non-sparking device
  5. At least (1) 4A-20-B: C rated portable fire extinguisher shall be located within 20 feet (towards the exit). No open flame or spark-producing devices shall be within 20 feet of spray space or vapor area (only approved electrical and heating devices allowed within a spray or vapor area)
  6. Existing built-in fire protection to be maintained.
  7. Submit floor plan (showing vapor area, potential ignition sources, openings to adjoining internal areas and items/areas of concern), MSDS for liquids to be used, description of operation and safety provisions (including emergency procedures, after-hours contacts, and equipment) with a document from the building's owner agreeing to such operations
  8. "No Smoking" signs shall be posted near spray space or vapor area and all safety procedures shall be enforced.

 

Download the Permit Application

Permit Holder Guideline #20

PERMIT TITLE: Fruit and Crop Ripening

CODE SECTION: (Virginia Statewide Fire Prevention Code) 2501.2

FEE: $200.00 Payable to the City of Richmond

SCOPE: An operational permit is required to operate a fruit – or crop-ripening facility or conduct a fruit-ripening process using ethylene gas.

EXCEPTION: Mixtures of ethylene and one or more inert gases in concentrations that prevent the gas from reaching greater than 25 percent of the lower explosive limit (LEL) when released to the atmosphere.

PERMIT EXPIRATION: ONE (1) year from the date issued.

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

  1. Ethylene gas shall be discharged only into approved rooms or enclosures designed and constructed for this purpose.
  2. Valves controlling the discharge of ethylene shall provide positive and fail-closed control of flow and shall be set to limit the concentration of gas in air below 1,000 parts per million (ppm).
  3. Sources of ignition shall be controlled or protected.
  4. Electrical wiring and equipment, including lighting fixtures, shall be approved for use in Class I, Division 2, Group C hazardous (classified) locations.
  5. Lighting shall be by approved electric lamps or fixtures only.
  6. Heating shall be by indirect means utilizing low-pressure steam, hot water, or warm air.

    Exception: Electric or fuel-fired heaters approved for use in hazardous (classified) locations, installed and operated per the ICC Electrical Code, the International Mechanical Code, or the International Fuel Gas Code.

  1. Containers, piping, and equipment used to dispense ethylene shall be bonded and grounded to prevent the discharge of static sparks or arcs.
  2. Empty boxes, cartons, pallets, and other combustible waste shall be removed from ripening rooms or enclosures and disposed of at regular intervals.
  3. Approved warning signs indicating the danger involved and necessary precautions shall be posted on all doors and entrances to the premises.

Download the Permit Application

Permit Holder Guideline #21

PERMIT TITLE: Fumigation – Insecticidal Fogging

CODE SECTION: (Virginia Statewide Fire Prevention Code) 2601.2

FEE: $300.00 for warehouse/complex and apartments, $200.00 for one or two family detached home, $200.00 for Confined area/vaults, $100.00 Thermal Insecticide Payable to the City of Richmond.

SCOPE: Need a permit from this office to do fumigation OR thermal insecticidal fogging within the City of Richmond (includes any use of gas, vapor, mist, fume or a similar process hazardous to humans within an enclosed space, for pest control).

PERMIT EXPIRATION: Duration of activity for A, B, E, I, M, or R use occupancies; up to annual for F, H, S, or U use occupancies and special enclosures as approved.

REQUIREMENTS: Apply for permit at least 10 days before event (with fee and 1 - 5 below). Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. Material Safety Data Sheet about fumigant.*
  2. Description of pest control process, including sealing of enclosed space to be affected, maintenance of existing fire protection systems, emergency procedures and after the event ventilation of affected rooms and adjoining enclosed spaces.*
  3. Sample of placard and emergency contact information. *
  4. Letter signed by owner (or person responsible for) of the building, requesting hazardous activity.*
  5. Certificate of insurance, when permit issued to party other than building owner and only tenant.
  6. Only people trained in use of fumigant are allowed in affected area during event.
  7. PLACARD ALL ENTRANCES to affected areas before event (remove after area made safe).
  8. The Fire Code Official shall be notified in writing not less than 48 hours before these spaces are closed in connection with the utilization of any toxic or flammable fumigant to include the location and approximate duration.
  9. Copy of the permit, MSDS and emergency contacts to be readily available on site during event.
  10. Open flames and other ignition sources shall be eliminated within affected area during event; only approved heat and electricity needed for fire protection system and special fans, may be on.
  11. Affected areas to be secured to prevent unauthorized entry during event with perimeter monitored by trained watch personnel (with #8 items: appropriate emergency rescue breathing apparatus and means to communicate emergency to city 911).
  12. Properly ventilate affected areas before un-securing or allowing others to occupy.

The use of carbon disulfide and hydrogen cyanide shall be restricted to agricultural fumigation only.

*Indicates that item must be submitted with the permit application.

Download the Permit Application

Permit Holder Guideline #22

PERMIT TITLE: Hazardous Materials

CODE SECTION: (Virginia Statewide Fire Prevention Code) 5001.5

FEE: $200.00 Payable to the City of Richmond) – ** (Per Warehouse)

SCOPE: An operational permit is required to store, transport on-site, dispense, use, or handle hazardous materials.

PERMIT EXPIRATION: ONE (1) year from the date issued.

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. Submit a Hazardous Materials Inventory Statement, a Hazardous Materials Management Plan, and a written emergency plan; and have available on site.
  2. Materials shall be properly stored and marked, plus hazard identification signs posted at the entry to those areas (NFPA 704). Material Safety Data Sheets (or reliable, quick electronic data) for all materials there shall be available on site.
  3. Approved 'No Smoking' signs (include symbol) shall be posted.
  4. Secure areas from unauthorized access, and separate incompatible materials.
  5. The area around outdoor storage shall be clear of combustible materials and vegetation for over 25 feet (30 feet for dispensing site).
  6. Safeguard containers from damage (including vehicular impact).
  7. Hazardous Materials in any quantity shall not be released into any sewer, storm drain, ditch, drainage canal, stream, river, lake, or tidal waterway nor on the ground, sidewalk, street, and highway or into the atmosphere.
  8. Where a release of hazardous materials gas or vapor would cause immediate harm to persons or property, means of mitigating the dangerous effects shall be provided by the property owner/company.
  9. Perform periodic audits to verify compliance with safety requirements.

Personnel responsible for the operation of areas where hazardous materials are used or stored shall be familiar with the chemical nature and the appropriate mitigating actions necessary in the event of a leak, spill, or fire.

Building’s safety features required by building code shall be maintained. Inspection and discussion of complexities of hazards and code applications will address more details.

Download the Permit Application

 

 

Permit Holder Guideline #23

PERMIT TITLE: Hazardous Production Materials (HPM)

CODE SECTION: (2015 Virginia Statewide Fire Prevention Code) /107.2/Chapter 50  

SCOPE:  Prevention Control and mitigation to dangerous condition related to storage dispensing, use and handling hazardous material. Maintain qualities IAW the Building Code. Chapter 50 applies to all hazardous material including those materials regulated elsewhere in the Virginia Statewide Fire Prevention Code. Specific requirements shall apply in Chapter 50 and IAW other applicable chapters in the Virginia Statewide Fire Prevention Code.

FEE:   $200.00    (Fee’s payable to the City of Richmond)

PERMIT EXPIRATION: One (1) year from date issued

REQUIREMENTS: An operational permit is required to store, transport on site, dispense, use or handle hazardous materials in excess of the amounts listed in Chapter 50 and others. Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on the permit, as well as the following:    

  1. Th
  1. Persons responsible for the operational areas shall be trained and familiar with chemical nature materials for mitigation of fires, leaks or spills. Preplanning emergency responses shall aid the fire department to the location of the hazardous material.

  1. Submit fire safety and evacuation plans, list of hazardous materials by quantities, site plan (noting locations of hazardous materials, and safety devices, including controls), how to contact key staff if emergency, and have copy available on site.  

  1. The Hazardous Material Management Plan shall include:

    1.  Access to each storage and use area
    2. Location of emergency equipment
    3. Location of where the liaison will meet emergency responders
    4. Facilities evacuation meeting point
    5. The general purpose of other areas within the building
    6. Location of all above – ground and underground tanks and their apparatus including, but not limited to sumps, vaults, below-grade treatment systems and piping
    7. The hazard classes in each area
    8. Location of all controlled areas and Group H occupancies
    9. Emergency exits

  1. Maintain a record quarterly drills conducted on-site emergency response team(s)

  1. All hazardous material containers, including carts and trucks shall be properly stored and marked. A hazardous identification sign located at the entrance area per (NFPA 704) shall be in clear view. Material Safety Data Sheets (or reliable, quick electronic data) for all hazardous materials shall be made available on site.

  1. Hazardous materials of any quantity shall not be released into any waterway, storm drain, river, lake, ground, side walk, street or into the atmosphere.

  1. The persons firm, or cooperation responsible for these unauthorized discharges shall institute and complete all actions necessary to remedy or the effects of such discharges. Such clean – up shall be the responsibility of the owner, firm, individual associated cost.

  1. Building’s safety features required by building code shall be maintained.  Inspection and      discussion of complexities of hazards and code applications will address more details. 

 

Download the Permit Application

 

Permit Holder Guideline #24

PERMIT TITLE:  High-Piled Combustible Storage

CODE SECTION: (2015 Virginia Statewide Fire Prevention Code) Chapter 32  

SCOPE: Maintenance and operational aspects of high-piled combustible storage shall be IAW Chapter 32, in addition to the requirements of chapter 32, the following material-specific requirements shall apply:

  1. Aerosols IAW Chapter 57
  2. Flammable and combustibles liquids IAW Chapter 57
  3. Hazardous materials IAW Chapter 50
  4. Storage of Combustible paper records IAW NFPA 13
  5. Storage of combustible fibers IAW Chapter 37
  6. General Storage of combustible material IAW Chapter 3

FEE: $200.00 (Fees payable to the City of Richmond)   

PERMIT EXPIRATION: Annual Permit 1 year after issued

REQUIREMENTS: An operational permit is required to use a building or portion thereof as a high-piled storage area exceeding 500 square feet. Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. Where required by the fire ode official, an evacuation plan for public accessible areas and a separate set of plans indicting location and width of aisles, exits, access doors, exit signs, height of storage and hazardous materials. This plan shall be submitted at the time of permit application for review and approval. After approval of such plan, a copy shall be maintained and remain on the premises.

  1. Chapter 37 and sections 3203 through 3203.7.4 lays out the commodity classification as a class I, II, III, IV or high hazard IAW sections enclosed. Classification of plastics shall be designated as Group A, B and C IAW chapter 32. High-piled storage areas shall be maintained IAW the building code requirements.

  1. Housekeeping and maintenance includes the structural integrity of racks, clearance shall prohibited from ignition sources. Smoking with is prohibited, Approved “No Smoking” signs shall be conspicuously posted. Racks shall be maintained.

  1. Aisles shall be kept clear of storage, waste materials and debris when not restocking. Fire Department access shall not be obstructed. Manual restocking operations require a minimum of unobstructed aisles of 24 inches and shall maintain 48 inches in smaller aisles. Unobstructed aisles widths of one-half (½) of the required aisle width shall be maintained if greater than 48 inches. Mechanical stocking of unobstructed aisles shall maintain 44 inches.

  1. All fire protection and life safety systems/features for high-piled storage areas shall be maintained. These systems include but are not limited to sprinkler systems, standpipe systems and heat/smoke alarms etc.

Download the Permit Application

 

Permit Holder Guideline #25

PERMIT TITLE:  Hot Works (Using Arc, Spark, or Flame Producing Devices)

CODE SECTION: (Virginia Statewide Fire Prevention Code) Chapter 35

SCOPE:  Welding, cutting, open torches, grinding, brazing, torch-applied roofing systems, or similar activities not limited to the above involving exposed arcing, sparks, flames, etc.

FEE: (All fees are payable to the City of Richmond) 

          [A] $100.00; Temporary pre-approved site(s) are site-specific

          [B] $200.00; City-wide, self-employed, independent, commercial contractor, etc. This permit allows for work throughout the City but is required at each location.  

PERMIT EXPIRATION: One (1) year from the date issued.

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instruction noted on the permit. An operational permit is required for hot work including, but not limited to:

  1. Public exhibitions and demonstrations where hot work is conducted

  1. Use of portable hot work equipment inside structure
    1. Exception: Work that is conducted under construction
  2. Fixed –site hot work equipment such as welding booths

  1. Hot work conducted within a hazardous fire area

  1. Application of roof covering with the use of an open – flame devices

  1. When approved, the fire code official shall issue a permit to carry out a Hot Work Program. This program allows approved personnel to regulate their facility’s hot work operations. The approved personnel shall be trained in fire safety aspects denoted in this chapter and shall be responsible for issuing permits requiring compliance with the requirements found in this chapter. These permits shall be issued only to their employees or hot work operations under their supervision.

  1. Fire safety requirements: protection of combustible hot work areas shall not contain combustibles and shall be provided with appropriate shielding openings or cracks in walls, floors ducts, or shafts. These hot work areas shall be tightly covered preventing sparks. Good housekeeping shall be kept clean within the hot work area.

  1. Hot works shall not be performed on containers or equipment that contain or have contained flammable liquids, gases, or solids. These containers shall be cleaned thoroughly purged, or inerted. Any “hot tapping” shall be conducted by a certified individual. Combustibles within six (6) inches of operations, 30 feet of hot embers, or sparking tools shall be protected by the provide method.

  1. A current certificate of insurance shall be on file in the Fire Marshal’s office. A copy of the requester’s insurance policy shall be given to the Fire Marshal’s Office and list them as the certificate holder. Submit a written safety procedure that lists operations being conducted to the Fire Marshal’s office and make available a copy for review at each job site.

  1. At least (1) 2A-20BC fire extinguisher shall be within 30 feet of the operator of the hot work, a 3A-40B, for a torch-applied roof system. Where combustibles are within 30 feet; a water hose is connected to a water supply. That water supply shall exceed 100 feet and a flow-controlled nozzle within five (5) of the operator. Two (2) 2 ½ gallon pressurized water extinguishers may be substituted with prior approval.

  1. A sign shall be posted (CAUTION) Hot Works in progress; persons not performing any work shall maintain a safe distance of no less than 10 feet where hot work is being conducted

  1. There is a required fire that shall be performed for a minimum of 60 minutes, additional instruction will be given as outline above should that be necessary.

 

Download the Permit Application

 

Permit Holder Guideline #26

PERMIT TITLE: Liquefied Petroleum Gases

CODE SECTION: (2015 Virginia Statewide Fire Prevention Code) Chapter 61

SCOPE: Storage handling and Transportation of liquefied petroleum gas LP-gas and the installation of LP-gas equipment pertinent to systems for uses shall comply with Chapter 61 and NFPA 58. Properties of LP-gas shall be determined in accordance with Appendix (B) of NFPA 58

FEE:  $200.00 Payable to the City of Richmond

PERMIT EXPIRATION: One (1) year from the date issued.

REQUIREMENTS: An operational permit is required for storage and use of LP-gas as outlined in Section 107.2. Distributors, shall not fill containers where a permit is required unless the installation has been issued one for location by the fire code official. All permit holders shall abide by the Virginia Statewide Fire Prevention Code, and NFPA 58 along with any special instructions noted on the permit

  1. Where construction is taking place and a single container of LP-gas is more than 2000 gallons in water capacity and the aggregate water capacity and the container is more than 4000 gallons the contractor shall submit construction documents to the fire code official.

  1. LP-gas containers located in buildings shall comply with Chapter 61 and additional code Sections outlined in the (VSFPC), portable LP-gas containers shall not be used in buildings and other areas i.e. basements, or similar locations above-grade underfloor spaces where heavier-than-air gas might collect. These locations have to be approved by the fire code official.

  1. Group F occupancies, portable LP-gas containers are allowed to be used to supply quantities necessary for processing, research, or experimentation. The aggregate water capacity for such containers shall not exceed 735 pounds. Where several manifold containers in the same room, they shall be separated by a distance not less than 20 feet.

  1. Group E and I facilities where LP-gas containers are allowed to be used for research, and experimentation shall not be used in classrooms. Such containers shall not exceed 50 pounds of water capacity in facilities used for educational purposes, and shall not exceed 12 pounds for institutional purposes. If these containers are in the same room, each container shall be separated by a distance not less than 20 feet.

  1. No “smoking “signs complying with (Section 310 of the VSFPC) shall be posted where required by the fire code official. LP-gas tanks shall maintain a distance of not less than 10 feet from weeds, tall grass, brush, trash, and other combustibles.

  1. LP-gas containers store in buildings are complying with Chapter 61 and associated sections shall not be located near exit doors, exits, stairways, or in areas normally used or intended to be used as a means of egress.

  1. A site plan identifying the location of LP-gas is required, an emergency evacuation plan is required and is subject to review by the fire code official. Emergency contacts shall be placed in a secure Knox-box and should be readily available for responding to fire companies. All LP-gas apparatus to include all attachments shall be protected to prevent damage from tampering and marked appropriately.

  1. Treat all empty containers as if they are containing flammable gas, before purging or released into the atmosphere, or removal of such tanks shall be coordinate with the fire code official.

  1. DOT cylinders are inspected and refilled on site one year after manufactured and every 5 years thereafter. Maintain at least a 4A-40B: C rated portable fire extinguisher every 15 to 30 feet depending on the facility's square footage.

Download the Permit Application

 

Permit Holder Guideline #27

PERMIT TITLE: Lumber Yards and Argo-Industrial Solid Biomass and Woodworking Facilities

CODE SECTION: (2015 Virginia Statewide Fire Prevention Code) Chapter 28

SCOPE: The storage manufacturing and processing of solid biomass feedstock, timber, lumber, plywood, veneers, and Argo-industrial by-products shall be in accordance with (IAW) chapter 28.   

FEE:  $200.00 Payable to the City of Richmond

PERMIT EXPIRATION: One (1) year from the date issued.

REQUIREMENTS: An operational permit is required for the storage or processing of lumber exceeding 100,000 board feet Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on the permit, as well as the following:

1.  Lumberyard/working plants –shall be equipped with approved combustible dust equipment with a dust collection and exhaust system that must be maintained. Systems that use or collect, process, or covey combustible dust shall provide an approved explosive control system.

2.  Reduce the accumulation of combustible dust build-up shall do a thorough and systematic cleaning to prevent static electricity from accumulating on machines and equipment. When performing cutting and welding, this operation shall comply with Chapter 35. Ignition control sources shall be IAW in Chapter 28. The fire code official is authorized to order the owner or operator to post “NO SMOKING” signs if smoking constitutes a fire hazard.  

3.  All fire protection systems shall be maintained, i.e. fire alarms, manual fire alarms, portable fire extinguishers, standpipe systems, automatic sprinkler systems, and approved fire hydrants protection IAW Chapter 28.  

4.  Log storage cold decks shall not exceed 500 feet in length, 300 feet in width, and 20 feet in height and other exposures shall be separated by no less than 100 feet. Hogged material, lumber production piles shall not exceed 60 feet in height, 300 feet in width, and 500 feet in length. Exterior solid Biofuel products shall be arranged to stable pile sizes with a maximum height of 20 feet, and shall not exceed 150,000 cubic feet. Fire access roads shall be maintained shall be IAW Chapter 5

       

5.  Emergency plans shall be developed by the owner or operator for monitoring, controlling, and extinguishing spot fires and submit the plan to the fire code official for review and approval.

Download the Permit Application

 

Permit Holder Guideline #28

PERMIT TITLE:  Fueled Vehicles /Equipment and Public Assembly Buildings to include but limited to warehouses

CODE SECTION: (2015 Virginia Statewide Fire Prevention Code) Chapter 3 

SCOPE:  This prevision of Chapter 3 shall govern the use for displaying, operating, or for demonstration of liquid and gas-fueled vehicles or equipment in the public assembly, warehouses, storage facilities, and premises. The pre-cautions will reduce all accidental fire spread to maintain the general requirements for fire safety.                   

FEE:  $200.00 – Operational Payable to the City of Richmond

PERMIT EXPIRATION: Thirty (30) days unless extended

REQUIREMENTS: An operational permit is required for indoor displays within the building or structure shall comply with chapter 3. The permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on the permit.

  1.   Where liquid or gas-fueled vehicles are not allowed to be in assembly or like facilities without the following exception:
  1. Negative battery terminal shall be disconnected
  2. Vehicle fuel tanks shall not exceed one-quarter (1/4) tank or 5 gallons whichever is less, motorcycles shall have no more than 1.5 gallons of fuel
  3. Fuel fill opening shall be  sealed and closed to prevent any tampering of vehicles while on display inside the building/facility
  4. Non – flammable materials or containers shall be placed beneath all vehicles to catch potential fluid leaks.
  5. All spills and or leaks shall be cleaned up immediately and those materials disposed of properly IAW the federal, state, and local requirements.
  6. While on display or demonstration vehicle electrical power packs(i.e.) battery packs shall be disconnected and remain until removed
  7. At the end of the vehicle display/demonstration, all vehicles shall be removed from the interior of the assembly building while occupied by the general public.
  8. All keys, key fobs, remoted key fob shall be stored in a secured location while being accessible at all times
  9. Egress, exit doors, exit pathways, and exit discharges shall remain clear and free from debris and other potential hazards      

2.  Compressed natural gas (CNG) or liquefied petroleum (LP) gas-powered vehicles shall have shut –off valve on the outlet of CNG or LP-gas container and shall remain closed while indoors and the engine is allowed to run until it shuts down 

  1. The positive terminals of CNG or LP-gas vehicles shall be disconnected. All vehicles shall be inspected for fuel levels, closed shut-off valves and electrical battery packs, etc., by the Fire Marshal’s office prior to entering the facility.

  1. A layout of the floor plan in which vehicles will rest shall be provided to the fire code official for review and approval prior to vehicles being placed inside the facility for display or demonstration.

Download the Permit Application

 

Permit Holder Guideline #29

PERMIT TITLE:  Magnesium (Flammable Solids)

CODE SECTION: (2015 Virginia Statewide Fire Prevention Code) Chapter 59

SCOPE: Storage use, handling, and processing of magnesium, including pure metal alloys which is a major part of magnesium, shall be IAW with chapter 59 and associated Sections of the VSFPC.              

FEE: $250.00 Payable to the City of Richmond

PERMIT EXPIRATION: One (1) year from the date issued.

REQUIREMENTS: An operational permit is required to melt, cast, heat treat, or grid more than 10 pounds of magnesium. Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. Before receiving a permit, submit a floor plan outlining hazardous material areas, (potential ignition sources and items/areas of concern), MSDS, description of operation, and safety provisions to include emergency procedures and equipment.

  1. A hazardous material permit is required if over 100 pounds of flammable solids are on site. The owner/ representative is required to contact the fire code official to conduct a full fire safety inspection before such permits being issued.

  1. The storage in foundries and processing plants include storage piles of magnesium that shall not exceed 1,250 cubic feet. Piles shall be separated by aisles with a minimum width of not less than one-half the piles' length.

    1. The storage of magnesium pigs, ingots, and billets shall comply with the VSFPC Section 5906 of Chapter 59.
    2. Indoor storage of magnesium pigs, ingots, and billets shall be maintained IAW Section 5906 of Chapter 59, the VSFPC, and any additional building codes. Piles shall be separated by aisles with a minimum width of not less than one –half the piles' length.
    3. Maximum indoor storage of 1000 cubic feet per pile and aisle width not less than the height of piles. Magnesium over 50 cubic feet per pile for fine scarp and open space not less than 50 feet wide shall have a constructed fire barrier separation from combustibles.
    4. Outdoor storage of magnesium, pigs, ingots, and billets shall be stored in piles not exceeding 1,000,000 pounds each. Piles shall be separated from combustibles materials or building on the same or adjoining property by a distance not less than the height of the nearest pile.

  1. Magnesium fine scrape shall be maintained and separated from other combustible material. Chips, turnings, and other fine magnesium scraps shall be collected from the pans or spaces under machines and from other places where they collect not-less than once a day. In an approved location this material shall be covered, vented in a steel container, and removed.

  1. Electrical wiring, fixtures, and equipment near attached dust-producing machines shall be maintained. Fire –extinguishing material shall be provided for every operator performing machining and other processing operation of magnesium. The following safety equipment at a minimum is required:

    1. Within 30 feet, a supply of extinguishing agent/material in an approved container with the availability of a hand scoop or shovel for applying to the material; or
    2. An approved portable fire extinguisher every 75 feet complying with NFPA 10

  1. “No Smoking” signs shall be posted and all safety procedures are enforced.

  1. Flammable solids shall are not allowed to be stored in the basement.

Download the Permit Application

Permit Holder Guideline #30

PERMIT TITLE:  Miscellaneous Combustible Storage

CODE SECTION: 2015 (Virginia Statewide Fire Prevention Code) Chapter 3

SCOPE: Combustible waste material

FEE: $200.00 Payable to the City of Richmond  

PERMIT EXPIRATION:  Annual

REQUIREMENTS:   An operational permit is required to store in any building or upon any premises in excess of 2000 cubic feet (160 square feet) gross volume of combustibles, empty packing cases, boxes, barrels or similar containers, rubber tires, rubber products, cork or similar combustible material and any combination thereof. The permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. Submit floor plans and site plans; showing locations of listed materials information on expected maximum amounts of materials and provisions for safety. A fire evacuation plan will be required as a part of the overall safety plan.

  1. Storage shall be orderly, not obstruct exits, and placed in a manner that is 10 feet away from any heat source to avoid ignition.

  1. Keep interior storage 2 feet below ceiling, or 18 inches below level of sprinkler heads.

Storage shall not be placed in boiler, mechanical or electrical rooms. 

  1. Outside storage maximum 20 feet high over 10 feet from lot line or other buildings on site.

Combustible materials shall not be stored or displayed under non-sprinkled eaves, canopies or other projections or overhangs of sprinkled buildings.       

  1. PROHIBIT outside storage of tires.

Tires may be outside as essential for display or business activities (must store inside approved structure otherwise). 

  1. Where outside storage exceeds 10,000 square feet, the following shall apply:

                                a. Piles shall not exceed 300 feet (91440 mm) in width and 500 feet (152 m) in length.

                                b. Separate piles by at least 20 feet wide and maintain fire vehicles emergency access aisles.

                                c. Keep weeds, debris or parked vehicles over 10 feet from piles. 

                                d. The owner or operator shall develop an emergency plan for monitoring, controlling and

                                    extinguishing small fires (promptly reporting fire to 911).

                     7.  "No Smoking" Signs Shall be Posted and Enforced for interior storage areas.

                     8.  Additional requirements may be based upon inspection and details of specific materials. 

                   Need other permits if have large amounts of combustible fibers, hazardous materials, wood or scrap tires (or tire by-products).  

Download the Permit Application

Food Truck Fire Safety Check List

Date:__________ Truck Name:_____________________________ Lic/VIN/Unit #___________________

Owners Name: _______________________  Business Address: _________________________________

Inspectors Name:_________________________________    Fire Dept. Phone # ____________________

LPG Containers and Piping

LPG piping is code compliant

Approved LPG containers

Containers installed outside or in vapor-tight cabinets accessible from outside

LPG containers mounted securely (SFPC 5303.5)

Containers protected against impact

Protection of cylinder valve

Shut off valve is readily accessible

Flexibility between the regulator and fixed piping

LPG cylinders shall not be installed, transported,        or stored inside the vehicle

No fueling or tank exchange during an event or with the public present

LPG Appliances (SFPC 5303.5, SFPC 5303.6)

All appliances installed on vehicles shall be approved

Appliances shall be readily accessible

Appliances shall be protected to minimize damage in transit

Appliances shall not block egress

Install permanent caution plate

Hood system (SFPC 904.4, 904.11.6)

Type 1 hood with grease-laden vapors

Fire ext. a system in the hood with tag

Proper ventilation and grease filters

Hood cleaned at regular intervals

Ext. system serviced every 6 mo.

Fire Extinguishers

All cooking vehicles 2A10BC (SFPC 906.3)

K extinguisher if required

Not in Service

LPG system shall be leak-free

Cylinders and/or containers shall be closed

The vehicle shall not be parked near heat sources, open flame, other ignition sources, or open pits.

Access

Fire apparatus access roads shall not be obstructed

Electrical (SFPC 605.1, SFPC 605.7)

Electrical hazards shall be abated

Electrical panels shall be accessible  

Extension cords shall not replace permanent wiring

No open junction boxes

Safe use of generators

General Requirements

No Smoking sign

No public in vehicle

Business license

No fueling during an event or with the public present

LPG gas detector installed

Comments:____________________________________________________________________________ __________________________________________________________________________________________________________________________________________________________________________

Owner/Operator Signature: _________________________ Approved Y   N     Approval Date: _________         Correction and Re-inspection required? Y   N 

The operator’s signature acknowledges they understand the line-items listed above and will abide by these requirements at all times. Keep your Permit visible or immediately available upon request.

 

Download the Permit Application

 

Permit Holder Guideline #32A

PERMIT TITLE: Open Burning  

CODE SECTION: (2015 Virginia Statewide Fire Prevention Code) Chapter 3

SCOPE: The provisions of this Chapter shall govern the occupancy and maintenance of all structures and premises for precautions against fire and the spread of fire and general requirements of fire safety.

FEE: $100.00 payable to the City of Richmond

PERMIT EXPIRATION: Operational Event only (duration period)

REQUIREMENTS: An operational permit for the kindling or maintaining of an open fire anyway public or private ground shall be followed. Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. Open burning shall only be allowed with prior approval from the fire code official providing that all conditions specified are authorized.

  1. Applications for open burning shall be submitted in writing at least ten days before the open burning event. Applications shall be submitted in the form of a letter addressed to the Fire Marshal and shall include the following information:

  • Fires must be constantly attended until extinguished and no longer smoldering
  • Attendees must provide adequate fire extinguishing equipment to control the fire
  •  Information regarding the purpose of the proposed burning
  • The nature and quantities of material to be burned
  • The location of the burning site
  • The date and time when open burning will take place
  • On-site fire extinguishing equipment to be provided

3.      Prohibited Burns:

  • Building and/or  demolition material
  • Household/ consumer trash or refuse
  • Paper, used lumber, or trade waste
  • Rubber tires, asphaltic material, crankcase oil, or impregnated wood
  • Toxic or hazardous materials or containers materials

4.     The location for any open burning shall not be less than 50 feet from any structure or combustible materials and provisions shall be made to prevent the fires from spreading to within 50 feet of any structure. Open burning shall be prohibited when atmospheric conditions or local circumstances make such fires hazardous.

                                                                                                                                                                      

  1. Where open burning creates or add to a hazardous environment, or requires a permit, it shall be prohibited when atmospheric conditions or the local fire code official believes such fires are hazardous. The responsible party is required to have at least one fire extinguisher 4-A rating or two 2-A ratings each or any other approved extinguishing agent. That agent can be dirt, sand, water in a barre, garden hose and shall be made available for utilization to include extinguishment.

Download the Permit Application

 

Permit Holder Guideline #32B

PERMIT TITLE: Open Burning - (***Bonfires***)

CODE SECTION: (2015 Virginia Statewide Fire Prevention Code) Chapter 3

SCOPE: A bonfire shall not be conducted within 50 feet of a structure or combustible material. Conditions that could cause a fire to spread within 50 feet of a structure shall be eliminated prior to ignition. This page outlines the requirements and prohibitions as well as permit application, inspection information to for bonfires conducted within the City of Richmond.

FEE: $40.00 payable to the City of Richmond

PERMIT EXPIRATION: Operational only duration of event

REQUIREMENTS: An operational permit is required for the kindling or maintaining of an open burning fire or fire on any public street, alley, and road or other public or private ground.

Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special Instructions noted on permit, as well as the following:

  1. The property owner should apply in writing, at least ten days before the event,  including the following information:
  • Provide the address/location of the bonfire
  • Provide the permit number
  • Provide the approximate duration of bonfire (3 hours maximum).
  • Obtain the event number for the notification and record it on the permit
  • Include the number of persons expected to attend.

                               

  1. Site Plan – a plat or site plan of the property shall be provided with the fire department application and shall show the following information:
  • Proposed location of the bonfire
  • Locations of all utilities such as gas  meters and overhead power lines
  • Location of structures and woodlands within 50 feet of the burn location
  • Location of the two closest fire hydrants and all fire department access routes

  1. Any open burning shall be constantly attended until the fire is extinguished.  Approved on-site fire extinguishing equipment, such as garden hoses, shall be available for immediate utilization.

  1. A bonfire shall not be more than 5 feet by 5 feet by 5 feet in dimensions and shall limited as outlined in section (1).

  1. Fuel for a bonfire shall consist only of seasoned dry firewood and shall be ignited with a small quantity of paper. The fire shall not be utilized for waste disposal purposes, and the fuel shall be chosen to minimize the generation of air contaminates.

  1. Hazardous Fires Prohibited: The fire code official or fire company may order the immediate extinguishment of any open burning or because of one or more of the following hazardous situations:

  • Unattended fires
  • Unprotected or uncontained fires deemed capable of spreading
  • Inadequate fire extinguishing equipment/ materials
  • Combustibles exposure hazards
  • Inappropriate or hazardous materials used as fuel
  • Air contaminates, smoke, or other materials which may cause a traffic hazard

Download the Permit Application

 

Permit Holder Guideline #32C

PERMIT TITLE: Open Burning - (Recreational Fires)

CODE SECTION: (2015 Virginia Statewide Fire Prevention Code) Chapter 3

SCOPE: Outdoor open fire burning for pleasure (back yard manufacture fire pits for residential use only), Religious, or Ceremonial purposes.

FEE: Contact the Fire Marshal’s Office

PERMIT EXPIRATION: Operational

REQUIREMENTS: Where a permit is required the permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following:

  1. Open burning may be allowed only after obtaining approval from the fire code official providing that all conditions specified are authorized for Recreational, Religion, and Ceremonial fires.

  1. Applications for open burning shall be submitted in writing at least ten days before the open burning event. Applications shall be submitted in the form of a letter addressed to the Fire Marshal and shall include the following information:

  • Fires must be constantly attended until extinguished and no longer smoldering
  • Attendees must provide adequate fire extinguishing equipment to control the fire
  •  Information regarding the purpose of the proposed burning
  • The nature and quantities of material to be burned
  • The location of the burning site
  • The date and time when open burning will take place
  • On-site fire extinguishing equipment to be provided

  1. Prohibited Burns:
  • Building and/or  demolition material
  • Household/ consumer trash or refuse
  • Paper, used lumber or trade waste
  • Rubber tires, asphaltic material, crankcase oil, or impregnated wood
  • Toxic or hazardous materials or containers materials

 

4.     The location for any open burning shall not be less 50 feet from any structure or combustible materials      and provisions shall be made to prevent the fires form spreading to within 50 feet of any structure. Open burning shall be prohibited when atmospheric conditions or local circumstances make such fires hazardous.

  1. Where open burning creates or add to a hazardous environment, or requires a permit, it shall be prohibited when atmospheric conditions or the local fire code official believes such fires are hazardous. The responsible party is required to have at least one fire extinguisher 4-A rating or two 2-A rating each or any other approved extinguishing agent. That agent can be dirt, sand, water in a barre, garden hose and shall be made available for utilization to include extinguishment.

Download the Permit Application

Permit Holder Guideline #32D

PERMIT TITLE: Open Pit Incinerator – (Trench Burning)

CODE SECTION: (2015 Virginia Statewide Fire Prevention Code) Chapter 3

SCOPE: Land Clearing/Property Maintenance, you can burn debris generated from the development of the property. This includes the removal of unwanted, leaning, hazardous or dead trees, regardless of size, during normal keep up or landscaping of the property. This could also include but is not limited to limbs, tree trunks, logs, and stumps.

FEE: $500.00 Payable to the City of Richmond                                            

PERMIT EXPIRATION: Operational – 30 Days

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special instructions noted on permit, as well as the following. The contractor/owner is required to have insurance to cover no less than $500,000.00 making the City of Richmond the certificate holder.

CONDITIONS FOR OPERATION

                                            

  1. Personnel shall be in attendance at all times during burning operations.

  1. All open-pit burning shall take place a minimum of 500 feet from any occupied structure excluding construction offices on the same property.

  1. Pit walls shall be essentially vertical and the pit shall have the following dimensions:

                                    Length - No longer than blower manifold

                                       Width - Eight (8) feet

                                       Depth - at least ten (10) feet

  1. The fan housing and manifold shall be assembled and maintained to prevent air leakage and the nozzle alignment shall provide a curtain of air in a plane aimed approximately two (2) to three (3) feet below the top of the pit edge opposite the manifold.

  1. At all times that there is a fire in the pit except for a twenty-minute start-up period; the blower shall be run at a speed sufficient to create an air curtain of sufficient velocity to deflect combustion gases downward into the pit.

  1. Building and demolition materials, paper, used lumber, trade waste, crankcase oil, plastic, impregnated wood, and other materials producing dense smoke shall not be burned.

  1. Garbage, household refuse, bedding, upholstered furniture, flooring covering, animal carcasses or animal waste shall not be burned.

  1. Toxic or hazardous materials or containers for such materials shall not be burned.

  1. Materials containing friable or non-friable asbestos shall be separated and not burned in the pit.

  1. Sellable timber and pulpwood shall not be burned.

  1. Stumps to be burned shall be free of dirt.

  1. At no time shall the pit be filled in such a manner that material to be burned is above the level of the air curtain. 

      Materials shall remain at least three (3) feet below the air curtain.

  1. Before removing ashes from the pit, they shall first be soaked with water.  No fires or burning embers are allowed outside the pit.  Ashes removed from the pit shall be disposed of in such a manner as to prevent their becoming airborne.

  1. Possession of this permit shall in no way limit the liability of the owner or operator for any damage that might result from the burning.

  1. A bulldozer, and/or water truck and an operator shall be on-site at all times during burning.

  1. On notification from the State Air Pollution Control Board that an air pollution episode is in progress; all burning shall be stopped until further notice.

Violation of any of the above requirements may result in the suspension of the permit.

 

Download the Permit Application

Permit Holder Guideline #32

PERMIT TITLE: Open Flame Device - Religious Ceremony Use in Assembly

CODE SECTION: (Virginia Statewide Fire Prevention Code) 308.1.7

FEE: $40.00 (Check payable to the City of Richmond)

SCOPE: A person shall not utilize or allow to be utilized, an open flame in connection with a public meeting or gathering for purposes of deliberation, worship, entertainment, amusement, instruction, education, recreation, awaiting transportation or similar purpose in assembly or educational occupancies without first obtaining a permit.

PERMIT EXPIRATION: Annual at own site, Operational elsewhere

REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

Any violations of these guidelines and/or the Virginia Statewide Fire Prevention Code shall result in permit revocation.

  1. Open flame decorative devices shall comply with the following:
    1. An approved non-flammable container to hold product to be ignited.
  2. Open flames shall not be located on or near decorative material or similar combustible materials.
  3. Open flame devices shall not be used in a Group A occupancy; except for the following:
    1. Ceremonial or Religious purposes
    2. On stage or platform theatrical performances
    3. Candles on tables are securely supported on noncombustible bases and the flame is protected.
  4. No decorative material shall be placed over open flame.
  5. All decorative materials shall be flame retardant.
  6. An approved method of extinguishment readily available during ceremony.
  7. A dedicated firewatch shall be held during ceremony.
  8. When not in own facility, application shall be co-signed by hosting site agent.

Any violations of these guidelines and/or the Virginia Statewide Fire Prevention Code shall result in permit revocation.

    Download the Permit Application

    Permit Holder Guideline #32A

    PERMIT TITLE: Open Flames - Theatrical Use in Assembly / Educational Facilities

    CODE SECTION: (Virginia Statewide Fire Prevention Code) 308.2

    FEE: $40.00 (Check payable to the City of Richmond)

    SCOPE: A person shall not utilize or allow to be utilized, an open flame in connection with a public meeting or gathering for purposes of deliberation, worship, entertainment, amusement, instruction, education, recreation, awaiting transportation or similar purpose in assembly or educational occupancies without first obtaining a permit.

    PERMIT EXPIRATION: Operational

    REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

    1. Open flame decorative devices shall comply with the following:
      1. No class I or class II liquids and LP-gas shall be used.
      2. Liquid or solid-fueled lighting devices containing more than 8 ounces of fuel must self-extinguish and not leak fuel at a rate of more than 0.25 teaspoon per minute if tipped over.
      3. Device or holder shall be designed to return to upright position after being tilted to an angle of 45 degrees from vertical.
      4. Device or holder shall be constructed to prevent the spillage of liquid fuel or wax at a rate of 0.25 teaspoon per minute when not in the upright position.
      5. Open flames shall not be located on or near decorative material or similar combustible materials.
    2. Open flames shall not be located on or near decorative material or similar combustible materials.
    3. Open flame devices shall not be used in a Group A occupancy, except for the following:
      1. Ceremonial or Religious purposes
      2. On stage or platform theatrical performances
      3. Candles on tables are securely supported on noncombustible bases and the flame is protected.
    4. Where approved by the fire code official, open-flame devices used in conjunction with theatrical performances are allowed to be used when adequate safety precautions have been taken in accordance with NFPA 160.

    Any violations of these guidelines and/or the Virginia Statewide Fire Prevention Code shall result in permit revocation.

    Download the Permit Application

    Permit Holder Guideline #32B

    PERMIT TITLE: Open Flames - Candles in Assembly / Educational Facilities

    CODE SECTION:(Virginia Statewide Fire Prevention Code) 308.3.2

    FEE: $40.00 (Check payable to the City of Richmond)

    SCOPE: A person shall not utilize or allow to be utilized, an open flame in connection with a public meeting or gathering for purposes of deliberation, worship, entertainment, amusement, instruction, education, recreation, awaiting transportation or similar purpose in assembly or educational occupancies without first obtaining a permit.

    PERMIT EXPIRATION: ONE (1) year from the date issued (annual or operational)

    REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

    1. Candles shall not be located on or near decorative material or similar combustible material.
    2. Candles shall be prohibited in the following areas: in aisles, exits or where occupants stand.
    3. Hand held candles shall not be passed from one person to another while lighted.
    4. Where approved candles used in conjunction with theatrical performances are allowed to be used when adequate safety precautions have been taken in accordance with NFPA 160.
    5. The device or holder shall be designed so that it will return to the upright position after being tilted to an angle of 45 degrees from vertical.
    6. Only candles in approved protected glass globe enclosures shall be used.
    7. All decorative materials shall be treated for flame retardance.
    8. The device or holder shall be constructed to prevent the spillage of liquid fuel or wax at the rate of more than .25 teaspoon per minute when the device or holder is not in an upright position.
    9. The device or holder shall be designed so that it will return to the upright position after being tilted to an angle of 45 degrees from vertical.

    Any violations of these guidelines and/or the Virginia Statewide Fire Prevention Code shall result in permit revocation.

    Download the Permit Application

    Permit Holder Guideline #32C

    PERMIT TITLE: Open Flames - Cooking Devices

    CODE SECTION: (Virginia Statewide Fire Prevention Code) 308.3.1

    FEE: $40.00 (Check payable to the City of Richmond)

    SCOPE: A person shall not utilize or allow to be utilized, an open flame in connection with a public meeting or gathering for purposes of deliberation, worship, entertainment, amusement, instruction, education, recreation, awaiting transportation or similar purpose in assembly or educational occupancies without first obtaining a permit.

    PERMIT EXPIRATION: Operational or Annual - ONE (1) year from the date issued or at the end of the event

    REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

    1. Liquefied-petroleum-gas-fueled cooking devices shall not be permitted inside or located within 20 feet of structure.
    2. Portable open flame cooking device shall not have a water capacity of greater than 2.5 pounds.
    3. Butane fueled portable cooking devices and sterno containers only (indoor use).
    4. Open flames shall not be located on or near decorative material or similar combustible materials.
    5. Charcoal burners and other open-flame cooking devices shall not he operated on combustible balconies or within 10 feet of combustible construction.
    6. The preparation of flaming foods or beverages in places of assembly and drinking or dining establishments shall be in accordance with section 308.1.8
      1. A 1 ounce container; or a container not exceeding 1-quart capacity with a controlled pouring device that limit the flow to 1-ounce per serving.
      2. Containers shall be secured to prevent spillage; when not in use.
      3. Flaming foods or beverages shall not be transported or carried while burning.
    7. The following units are considered to be a minimal hazard and are typically approved for usage inside: Microwave Ovens, Crock Pots, Toasters, Popcorn Machines, Food Warmers, Hot Dog Rollers and Fry Top Griddle.
    8. The following units are considered to be open flame/high hazard devices and are typically approved for use with adequate separation from the public: Deep Fat Fryers, Open Burner Stoves or Ranges, and Char Broilers. Seating for food consumption shall be at least 20 feet from these high hazard devices.
    9. Each cooking site shall be equipped with one portable dry chemical fire extinguisher with a minimum rating of 4A-20BC in good working order (minimal hazard devices); Class 'K' type fire extinguisher and 'ABC' type fire extinguishers (high hazard devices).
    10. All commercial cooking equipment including high hazards devices shall be protected by an approved automatic fire extinguisher hood suppression system when cooking produces grease laden vapors.
    11. All waste grease shall be stored in metal containers with tight-fitting lids until properly removed from the site.
    12. All special events with cooking functions shall be reviewed and approved by the Fire Marshal’s office and are to be inspected anytime during cooking operations.

    Download the Permit Application

    Permit Holder Guideline #32D

    PERMIT TITLE: Open Flames - Paint Removal

    CODE SECTION: (Virginia Statewide Fire Prevention Code) 308.1.3

    SCOPE: To use torch or open flame for removing paint from a structure.

    FEE: $40.00 (Check payable to the City of Richmond)

    PERMIT EXPIRATION: Operational or Annual- ONE (1) year from date issued. Building's owner to perform work on their own property. All contractors performing work within city limits. Permit holder shall be the operator of permitted operation or on site during the duration of the operation.

    REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

    1. Torch or open flame may only be used on exterior surfaces. Operations will cease when wind speeds rise to over 10 miles per hour.
    2. A water hose shall be in place and ready for use within 5 feet of the torch operator. (If there is no water source available, the operator shall have at least one 4A rated, or two 2A rated portable fire extinguishers on site and ready for operation.)
    3. The contractor shall instruct all operators on the safe and efficient use of the particular device being used along with the risks associated with this type of operation (specifically the possibility of hidden fires in combustible structures). This instruction shall include, but not be limited to, the exact operation of the particular device and its' limitations and safety features. Additionally the contractor shall instruct the operator on telltale signs of hidden fires in structures and how to interrupt their progression. All of this instruction shall be documented and maintained in possession of the contractor for review.
    4. The contractor / operator shall inspect and discuss all safety concerns with the building’s owner and tenant. This discussion shall include all proper safety procedures currently in place, all risks relative to this type of operation and all details pertaining to the emergency action plan in place for the particular operation, including, but not limited to, the means to promptly report unwanted fires to 911 along with the exact conditions and situation (including address, injuries, or special circumstances). This requirement shall mandate that either a hard wired telephone line and/or a fully charged and operable cellular telephone be on site and readily accessible to both the operator(s) and/or the owners / tenants.
    5. All permit holders shall have on file with the Fire Marshal's office a copy of their current liability insurance policy (required to be at least twice the value of the building and not less than $1,000,000) along with a copy of all related safety procedures. Said insurance policy shall confirm coverage for paint burning operations on structures.
    6. A copy of this permit shall be at the job site at all times during the operation and available for official review.
    7. The operator / Contractor shall provide a firewatch during the entirety of the operation and extending for 2 hours after open flame operations have concluded. This firewatch shall include monitoring of the interior and / or other connected areas affected by the paint burning operation. A battery-powered smoke detector must be provided for 24 hours subsequent to the operation in all occupied buildings.

    The public health official shall be contacted prior to commencement of the operation if there is any possibility the structure contains lead-based paint. In the event that lead based paint is present additional regulations may apply.

     

    Any violation of these guidelines; the Virginia Statewide Fire Prevention Code; or occurrence of fire damage as a result of paint burning operations shall result in permit suspension. After suspension of the applicants permit and appropriate improvements said applicant may apply for a conditional permit from the Fire Marshal's Office after a 6 month period. If a conditional permit is issued it would directly address the applicant's deficiencies and require the appropriate corrections. These corrections shall include the hiring of an off duty fire official to be on site during all of the applicants subsequent paint burning operations to supervise these operations. Said fire official shall be hired at the current off duty pay rate (currently $27.00 per hour / 4 hour minimum) and shall be paid at conclusion of the operation by the applicant.

     

    A second violation of the above listed codes shall result in a permanent revocation of the applicants permit.

     

    Download the Permit Application

    Permit Holder Guideline #34

    PERMIT TITLE: Organic Coatings

    CODE SECTION: (Virginia Statewide Fire Prevention Code) 2901.2

    FEE: $250.00 Payable to the City of Richmond

    SCOPE: Permit required for any organic-coating manufacturing operation producing more than 1 gallon of an organic coating in one day.

    DEFINITION: Organic Coating is a liquid mixture of binders such as alkyd, nitrocellulose, acrylic, or oil and flammable and combustible solvents such as hydrocarbon, ester, ketone, or alcohol, which, when spread in a thin film, convert to a durable protective and decorative finish.

    PERMIT EXPIRATION: ONE (1) year from the date issued.

    REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

    1. Open flames and direct-fired heating devices PROHIBITED in areas with flammable vapors. "No Smoking" signs shall be posted and enforced.
    2. Organic coatings initiators shall not be contaminated with foreign substances.
    3. Spray guns and related handling equipment used with organic peroxides shall be of a type manufactured for such use.
    4. Separate pressure vessels and inserts specifically for the application shall be used for the resin and for the organic peroxide and shall not be interchanged. Organic coatings pressure tank inserts shall be constructed of stainless steel or polyethylene.
    5. Residue control shall be maintained. Spill material shall be properly removed.
    6. Spraying operations shall be conducted in approved spray booths, see Permit Guide #38.
    7. Ground and electrically bond containers (including tanker vehicles) during fluid transfer. Empty flammable or combustible liquid containers shall be removed to outside.
    8. Handling shall be conducted in a manner that avoids shock and friction that produces decomposition and violent reaction hazards.
    9. Organic coatings shall not be mixed directly with accelerators or promoters.
    10. Only non-sparking tools shall be used in areas where organic coatings are stored, mixed, or applied.
    11. Personnel working with organic coatings shall be specifically trained to work with these materials.

    Download the Permit Application

    Permit Holder Guideline #35

    PERMIT TITLE: Pyroxylin (Cellulose Nitrate) Plastics

    CODE SECTION: (Virginia Statewide Fire Prevention Code) 4201.2

    FEE: $200.00 Payable to the City of Richmond

    SCOPE: The storage and handling of plastic substances, materials, or compounds with cellulose nitrate as a base, by whatever name is known, in the form of blocks, sheets, tubes or fabricated shapes shall require a permit.

    PERMIT EXPIRATION: ONE (1) year from the date issued.

    REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

    1. Cellulose nitrate (pyroxylin) plastic articles are allowed to be placed on tables not more than 3 feet (914 mm) wide and 10 feet (3048 mm) long. Tables shall be spaced at least 3 feet (914 mm) apart. Where articles are displayed on counters, they shall be arranged in a like manner.
    2. Spaces underneath tables shall be kept free from the storage of any kind and accumulation of paper, refuse, and other combustible material.
    3. Sales or display tables shall be so located that in the event of a fire at the table, the table will not interfere with free means of egress from the room in at least one direction.
    4. Lighting shall not be located directly above cellulose nitrate (pyroxylin) plastic material unless provided with a suitable guard to prevent heated particles from falling.
    5. Raw nitrate (pyroxylin) plastic material in a Group F building shall be stored and handled in accordance with sections 4204.1.1 through 4204.1.7 of the Virginia Statewide Fire Prevention Code.
    6. The manufacture or storage of articles of cellulose nitrate (pyroxylin) plastic in quantities exceeding 100 pounds (45 kg) shall be located in a building or portion thereof equipped throughout with an approved automatic sprinkler system in accordance with section 903.3.1.1 of the Virginia Statewide Fire Prevention Code.
    7. Sources of ignition shall not be located in rooms in which cellulose nitrate (pyroxylin) plastic above 25 pounds (11 kg) is handled or stored.
    8. Rooms in which cellulose nitrate (pyroxylin) plastic is handled or stored shall be heated by low-pressure steam or hot water radiators.

     

    Download the Permit Application

    Permit Holder Guideline #36

    PERMIT TITLE: Repair Garages and Services Stations

    CODE SECTION: (Virginia Statewide Fire Prevention Code)

    SCOPE: Automotive motor fuel-dispensing facilities, marine motor fuel-dispensing facilities, fleet vehicle motor fuel-dispensing facilities and repair garages shall be in accordance with Virginia Uniform Statewide Building Code, International Fuel Gas Code, International Mechanical Code, and the Virginia Statewide Fire Prevention Code. Such operations shall include both operations that are accessible to the public and private operations.

    FEE: $100.00 Payable to the City of Richmond

    PERMIT EXPIRATION: ONE (1) year from the date issued

    REQUIREMENTS: Repair Garages for vehicles that use at least one type of fuel shall comply with the applicable provisions of the Virginia Uniform Statewide Building Code and Virginia Statewide Fire Prevention Code. Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

    REPAIR GARAGES: An operational permit is required for operating repair garages, automotive, marine, and fleet service stations to include self-service fueling stations.

    Services Stations:

    1. Accurate inventory records shall be maintained on underground fuel storage tanks for an indication of possible leakage from tanks and piping. The records shall be kept at the premises or made available for inspection by the fire official within 24 hours of written or verbal request and shall include records for each tank.
    2. Portable fire extinguisher in accordance with the section 906 Virginia Statewide Fire Prevention Code, having a minimum rating of 2-A: 20-B: C shall be provided and location such that an extinguisher is not more than 75 feet from pumps dispensers or storage tank fill-pipe opening.
    3. Warning signs shall be conspicuously posted within sight of each dispenser in the fuel-dispensing area and shall state the following:
      1. It is illegal and dangerous to fill unapproved containers with fuel.
      2. Smoking is prohibited.
      3. The engine shall be shut off during the refueling process.
      4. Portable containers shall not be filled while located inside the truck, passenger compartment, or truck bed of a vehicle.
    4. The fenced and diked area surrounding above-ground tanks shall be kept free from vegetation, debris, and other material that is not necessary to the proper operation of the tank and piping system.

    Repair Garages: Repair garages are not limited to any one type of fuel, but any internal combustible vehicle that is powered by the likes of gasoline, diesel, etc. These garages maintain your vehicle to ensure serviceability or make repairs that are not limited to transmission, mufflers, etc.

    1. The cleaning of parts shall be conducted in listed and approved parts-cleaning machines.
    2. Waste oil, motor oil shall be stored in approved tanks or containers, which are allowed to be stored and dispensed from inside repair garages.
    3. Smoking shall not be permitted in repair garages except in approved locations.
    4. For vehicles powered by gaseous fuel, the fuel shutoff valves shall be closed before repairing any portion of the vehicle fuel system.
    5. Vehicles powered by gaseous fuels in which the fuel system has been damaged shall be inspected and evaluated for fuel system integrity before being brought into the repair garage. Test the entire fuel delivery system for leakage.
    6. The battery terminals shall be disconnected from the battery while repair operations are being performed.
    7. Fire extinguishers shall be provided in accordance with section 906 Virginia Statewide Fire Prevention Code, with a minimum of 2-A: 20-B: C shall be provided in locations not more than 50 feet maximum travel distance to extinguishers.

     

    Download the Permit Application

    Permit Holder Guideline #37

    PERMIT TITLE: Rooftop heliport

    CODE SECTION: (Virginia Statewide Fire Prevention Code) 1101.3

    FEE: $600.00 Payable to the City of Richmond

    SCOPE: Permit required for operating a rooftop heliport. Other permits are needed if fuel is stored beyond aircraft or vehicle. Contact us if refueling on roof.

    PERMIT EXPIRATION: ONE (1) year from date issued.

    REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code, any special stipulations noted on the permit, as well as the following:

    1. Limit activities to approved areas (per building code and fire code official's inspection).
    2. Submit copy of site plan and building floor plans approved by building official and documentation that rooftop helicopter operations approved by the FAA. Please include information as to the number and largest helicopter capable of using this heliport.
    3. The touchdown area shall be surrounded on all sides by a clear area having a minimum average width at roof level of 15 feet but no width less than 5 feet.
    4. Landing area shall be maintained so as to confine flammable or Class II combustible liquid spills to the landing area and provisions shall be made to drain such spillage away from exits. Activities in area affected by a fuel spill shall be restricted to the mitigation of that spill until the hazard is removed or mitigated. Promptly report all spills to the Fire Marshal’s office.
    5. All portions of the heli-stop and heliport shall be within 150 feet of a 2.5 inch standpipe outlet (an approved location readily usable for firefighting on that facility).
    6. At least (1) 80-B: C rated extinguisher readily available during activity at long-term helipad area.
    7. Aircraft operation area and related areas shall be kept free of combustible debris at all times.
    8. Copy of permit, MSDS for fuels, and emergency contact information shall be readily available on site during activities. Please submit copy of emergency provisions and procedures including during weather with lightning nearby.
    9. Contact us for additional requirements if plan to refuel, service or store helicopters on roof or in the building.

     

    Download the Permit Application

    Permit Holder Guideline #38

    PERMIT TITLE: Spraying and Dipping

    CODE SECTION: (Virginia Statewide Fire Prevention Code) 1501.2

    SCOPE: A permit to conduct a spraying or dipping operation utilizing flammable or combustible liquids, or the application of combustible powders.

    FEE: $200.00 Payable to the City of Richmond)

    PERMIT EXPIRATION: ONE (1) year from the date issued.

    REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

    1. Submit a description of operation (including the maximum amount of hazardous materials, with MSDS for each), safety provisions, and the floorplan showing the location of operation (including the size of tanks). Area to comply with building, electrical, and other applicable codes.
    2. Electrically ground metal in spray area (including workpieces). Electrically bond containers when transferring flammable mixture. Containers supplying spray nozzles shall be closed.
    3. Required exhaust or ventilation system to be on when spraying.
    4. Containers and piping to which a hose or flexible connection is attached shall have a shut-off valve at the connection; and that keep valve closed when hose not in use. An approved relief valve shall be provided where flammable or combustible liquids are supplied to spray nozzles by positive displacement pumps.
    5. Post and enforce "No Smoking" signs. No open flames within 20 feet of the spray area. Welding, cutting, and similar spark-producing operations shall not occur in or near spray areas or dipping or coating operations unless proper safety is provided. Only non- sparking tools shall be used in areas where organic coatings are stored, mixed, or applied.
    6. Protect against the accumulation of vapors, self-ignition, and excessive heat where heat is involved.
    7. Residue control shall be maintained. Spill material shall be properly removed. Spraying areas, including exhaust duct, to be kept free from accumulation of deposits of combustible residue. Cleaning tools to be of non-sparking materials. Used rags, filters, residue, and waste to be put in self-closing, non-combustible containers, emptied at the end of each shift (at least daily).
    8. Not use the same spray area with materials susceptible to spontaneous heating and ignition, or otherwise react, without removing all deposits from the area; including exhaust, and change filters.
    9. Portable fire extinguishers per NFPA 10 (appropriate for hazard). Maintain and periodically inspect and test fire protection devices and systems per code. Staff trained for emergencies.
    10. Handle organic peroxides to avoid shock and friction that produces decomposition and violent reaction hazards.
    11. Dip tanks and drainboards must be of non-combustible materials; their supports of heavy metal, reinforced concrete, or masonry (all to comply with NFPA 34). Tanks over 150 gallons or 10 square feet liquid surface area to have trapped overflow pipe to outside, and an automatic fire- extinguishing system or automatically closing cover (capable of manual operation). Tanks over 500 gallons shall automatically drain quickly if fire (with the ability for manual operation at a safe location), to an approved outside location. Conveyor systems shall automatically stop if fire.
    12. Electrostatic apparatus and devices used for paint-spraying or pain-deterring operations shall:
      1. Have signs noting sparking distance and to keep items twice that distance away.
      2. Have signs designating the process zone as dangerous for fire and accidents, identifying grounding requirements for all conductive materials in spray area (including persons), and the area restricted to qualified personnel only.
      3. Interlock hand electrostatic equipment so cannot operate unless the ventilation system on.
      4. Automatically disconnect the power supply to the high-voltage transformer and signal the operator when any of the following occur:
        1. Ventilation fan stops or fails
        2. Stoppage of conveyor carrying articles past the high-voltage grid
        3. The occurrence of ground or an imminent ground at any point of the high-voltage system
        4. Reduction of clearance less than twice the sparking distance
    13. Additional permits may be required to handle or store hazardous materials, or to use torch or arc to cut or weld and similar "hot work". An inspection of your facility is required before these permit applications will be processed.

    Download the Permit Application

    Permit Holder Guideline #39

    PERMIT TITLE: Tires

    CODE SECTION: (Virginia Statewide Fire Prevention Code) 2501.2

    FEE: $200.00 Payable to the City of Richmond)

    SCOPE: Storage, handling tires or tire by-products over 2,500 cubic feet, or tire rebuilding.

    PERMIT EXPIRATION: ONE (1) year from the date issued.

    REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

    1. NO OUTSIDE TIRE STORAGE. Tires, and parts thereof, may be outside only for display or handling needs during business activities.
    2. Storage to be orderly. When indoors, not within 2 feet of ceiling nor obstruct an exit.
    3. Post “NO SMOKING” sign and enforce within 10 feet where storing over 10 tires.
    4. At least a 2A-20BC rated portable fire extinguisher to be within 40 feet.
    5. Tires stored adjacent to or along one wall shall not extend more than 25 feet from that wall. Other piles shall not be more than 50 feet in width. Tires not to be stacked over 8 feet high, unless on non-combustible racks in sprinklered area. No storage within 10 feet of a lot line or 15 feet from a building not part of this business (over 25 feet if residential with the combustible exterior).
    6. Submit site plan showing surrounding buildings, topographic, and construction features (including on-site surface drains, if any); plus an emergency action plan, including procedures to minimize fire run-off hazards.
    7. Submit a copy of the tire disposal procedure that is being used.
    8. Tire buffing area to be frequently cleaned, put debris in a fire-resistant container until removed from premises.

     

    Download the Permit Application

    Permit Holder Guideline #40

    PERMIT TITLE: Tents and Membrane Structures

    CODE SECTION: (Virginia Statewide Fire Prevention Code) 2403.4

    FEE: $100.00 Payable to the City of Richmond

    SCOPE: Any temporary tents, canopies, air-supported, air-inflated, and tensioned membrane structures.

    PERMIT EXPIRATION: Operational: A period not to exceed 180 days within 12 months on a single location.

    REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

    1. Tents and membrane structures shall not be located within 20 feet of lot lines, other structures, parked vehicles, or internal combustion engines.
    2. All tent fabric shall meet the flame resistance requirements; documented by permanently attached labels and/or certificates of compliance with NFPA 701 and flame resistance is effective for the period of the permit.
    3. Exit signs and emergency egress lighting may be required if:
      • The event is being held after dark
      • Utilization of side panels
      • Occupancy load of 50 or more persons
      • Travel distance to an exit from all points within the structure shall not exceed 100 feet

    All exit signs shall be illuminated at all times that structures are occupied. Backup power shall be provided for exit signs, egress lighting, and exit discharge lighting. Exit signs shall be an approved self-luminous type.
     

    1. All combustible materials such as hay, straw, shavings, or similar materials shall not be located within any structure containing assembly occupancy. Combustible materials or vegetation within 20 feet of a structure shall be maintained clear. Combustible trash shall be removed at least once a day from the structure while it is occupied by the general public.
    2. There shall be a minimum clearance of 3 feet between the fabric envelope and all contents located inside the tent or membrane structure.
    3. All fire extinguishers shall not exceed 75 feet travel distance and have a minimum rating of 2-A and shall be provided for all tents or structures.
    4. Smoking shall not be permitted in tents or membrane structures.
    5. No cooking or open flame shall be located in (or within 20 feet) a tent used for assembly.

     

    Download the Permit Application

    Permit Holder Guideline #41

    PERMIT TITLE: Tire Rebuilding and Tire Storage.

    CODE SECTION: (Virginia Statewide Fire Prevention Code) 2301.2 && 2501.2

    FEE: $200.00 Payable to the City of Richmond

    SCOPE: An annual permit is required for the operation and maintenance of a tire rebuilding plant, or to establish, conduct, or maintain over 2,500 cubic feet of scrap tires and tire byproducts. (See permit #39 for tires storage.)

    PERMIT EXPIRATION: ONE (1) year from the date issued (annual).

    REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

    1. Construction - Tire rebuilding plant shall comply with the requirements of the Virginia Uniform Statewide Building Code; as to construction, separation from other buildings, or other portions of the same building and protection.
    2. Buffing operations shall be in a room; separated from the remainder of the building housing the tire rebuilding or tire recapping operations by a 1-hour fire barrier (unless otherwise approved by a city building official).

                      Exceptions:

      1. Buffing operations are equipped with an approved continuous automatic water spray system directed at the point of cutting action.
      2. Buffing machines are connected to particle collecting systems providing a minimum air movement of 1,500 cubic feet per minute in volume and 4,500 feet per minute in- line velocity.
      3. The collecting system shall discharge the rubber particles to an approved outdoor noncombustible or fire-resistive container, which is emptied at frequent intervals to prevent overflow.
    1. The buffing area shall be cleaned at frequent intervals to prevent the accumulation of rubber particles.
    2. Spray rooms and booths - See permit guide # 34 if spray or dip using combustibles medium.
    3. Open Burning - Open burning is prohibited in tire storage yards.
    4. Sources of heat - Cutting, welding, or heating devices shall not be operated in tire storage yards.
    5. Smoking prohibited - Smoking is prohibited in tire storage yards, except in designated areas.
    6. Power lines - Tire storage piles shall not be located beneath electrical power lines having a voltage above 750 volts or that supply power to fire emergency systems.
    7. Fire Safety Plan - The owner or individual in charge of the tire storage yard shall be required to prepare and submit to the fire code official a fire safety plan for review and approval. The fire safety plan shall include provisions for fire department vehicle access. At least one copy of the fire safety plan shall be prominently posted and maintained at the storage yard.
    8. Telephone number - The telephone number of the fire department and location of the nearest phone shall be posted conspicuously in attended locations.

    Outdoor Storage

    1. Section 46.1-58 of the Richmond City Code prohibits outside storage of tires, tire pieces, or combustible byproducts. Such items may be outside for display and handling during business hours when staffed and supervised.

    Indoor Storage Arrangement

    1. Pile dimensions - Where tires are stored on the tread, the dimensions of the pile in the direction of the wheel hole shall not be more than 50 feet. Tires stored adjacent to or along one wall shall not extend more than 25 feet from that wall. Other piles shall not be more than 50 feet in width.

     

    Download the Permit Application

    Permit Holder Guideline #42

    PERMIT TITLE: Waste Material Handling Facility - Junk Yards

    CODE SECTION: (Virginia Statewide Fire Prevention Code) 107.2

    FEE: $200.00 Payable to the City of Richmond

    SCOPE: A permit is required to operate a wrecking yard, junkyard, or waste material-handling facility.

    PERMIT EXPIRATION: ONE (1) year from the date issued (annual)

    REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

    1. Permit applicant to submit a site plan showing structures, lot lines, fences (and other barriers), topography, accumulation areas (describing the type of material, such as if combustible loose fibers vs. equipment with a mixture of mostly metal with some combustible components), fire vehicle access routes, hydrants, water-ways, drainage, and similar information relevant to risk management of fire or environmental emergencies.
    2. The site operator shall submit an emergency contingency plan, including descriptions of resources available on-site and those which can arrive within an hour; plus names and phone numbers for after-hours emergency response.
    3. Combustible waste material shall be properly contained when beyond areas approved for extensive accumulated storage.
    4. Control weeds, grass, vines, or other growth to minimize fire risk within 15 feet from combustible storage or combustible structures.
    5. Outside storage of combustible materials shall not exceed 10 feet above nor below the nearby surrounding area’s average grade level.
    6. The surface area of each accumulation of combustible materials shall not exceed 300 feet in length or width.
    7. An approved fire vehicle access route shall be within 150 feet of all areas of combustible accumulations, plus between such accumulations and lot line.
    8. A fire hydrant, capable of 1,000 gallons per minute flow, shall be along the fire vehicle access route within 400 feet of any area of combustible accumulation over 100,000 cubic feet. At least 700 feet of approved 2.5” diameter firefighter hose to be available for each hydrant.

    See Permit Guide #25 before using a torch or other 'Hot Work'.

    Outside storage of tires is prohibited by city code #46.1-64. Contact us and see Permit Holder Guideline #39 if plan to have many tires. (other than mounted on vehicles).

     

    Download the Permit Application

    Permit Holder Guideline #43

    PERMIT TITLE: Wood Products

    CODE SECTION: (Virginia Statewide Fire Prevention Code) 1901.2

    FEE: $200.00 (Check payable to the City of Richmond)

    SCOPE: An operational permit is required to store wood chips, hogged material, lumber, or plywood over 200 cubic feet (6 cubic meters).

    PERMIT EXPIRATION: ONE (1) year from the date issued.

    REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:

    1. A permit shall constitute permission to store or handle materials or to conduct processes in accordance with the Virginia Statewide Fire Prevention Code., and shall not be construed as authority to omit or amend any of the provisions of this code. Permits shall remain in effect until revoked or for such period as specified on the permit. Permits are not transferable. Before a permit is issued, the fire official shall make such inspections or tests as are necessary to assure that the use and activities for which application is made comply with the code.
    2. Open Yards. Open yards required by the Virginia Uniform Statewide Building Code shall be maintained around structures.
    3. Dust Control. Equipment or machinery located inside buildings that generate or emits combustible dust shall be provided with an approved dust collection and exhaust system. Equipment or systems that are used to collect, process, or convey combustible dust shall be provided with an approved explosion control system.
    4. Explosion Venting. Where a dust explosion hazard exists in equipment rooms, buildings, or other enclosures, such areas shall be provided with explosion (deflagration) venting or an approved explosion suppression system. Exception: Manual waste removal when approved.
    5. Housekeeping. Provisions shall be made for a systematic and thorough cleaning of the entire plant at sufficient intervals to prevent the accumulations of combustible dust and spilled combustible or flammable liquids.
    6. Metal Scrap. Provision shall be made for separately collecting and disposing of any metal scrap so that such scrap will not enter the wood handling or processing equipment.
    7. Protect combustibles (such as wood) from ignition sources.
    8. Hot work shall comply with the City of Richmond Permit Holder Guideline #25.
    9. Static electricity shall be prevented from accumulating on machines and equipment subject to static electricity buildup by permanent grounding and bonding wires or other approved means.
    10. Post and enforce "No Smoking" signs in areas of combustible (wood) work or storage.
    11. Fire apparatus access roads shall allow a fire truck, under all weather conditions, within 150 feet of the exterior of any building or storage stack.
    12. Where storage pile configurations could change because of changes in product operations and processing, the access plan shall be submitted for approval when required by the fire code official.
    13. Portable fire extinguishers shall be provided for extra-high hazards. Portable fire extinguishers with a minimum rating of 4-A:60-B: C shall be provided on all vehicles and equipment operation on piles and at all processing equipment.
    14. Plant operations of plywood, veneer, and composite board mills shall comply with Permit Holder Guideline #27.
    15. Cold decks shall not exceed 500 feet (152.4 m) in length, 300 feet (91440 mm) in width, and 20 feet (6096 mm) in height. Cold decks shall be separated from adjacent cold decks or other exposures by a minimum of 100 feet (30480 mm). Exception: The size of cold decks shall be determined by the fire code official where the decks are protected by special fire protection.
    16. Log and pole piles shall be stabilized by approved means.
    17. The storage of wood chips and hogged materials associated with timber and lumber production facilities shall comply with Permit Holder Guideline #27.
    18. Piles shall not exceed 60 feet (18288 mm) in height, 300 feet (91440 mm) in width, and 500 feet (152 m) in length. Piles shall be separated from adjacent piles or other exposures by approved fire apparatus access roads.
    19. The owner or operator shall develop an emergency plan for monitoring, controlling, and extinguishing spot fire. These plans shall be submitted to the fire code official for review and approval.
    20. The storage and processing of wood chips, hogged materials, fines, compost, and raw product produced from yard waste, debris, and recycling facilities shall comply with this section.
    21. Storage sites shall be level and on solid ground or another all-weather surface. Sites shall be thoroughly cleaned before transferring wood products to the site.
    22. Piles shall not exceed 25 feet in height, 150 feet in width, and 250 feet in length.
    23. Control the storage, accumulation, and handling of combustible materials and vegetation.
    24. Static piles shall be monitored by an approved means to measure temperatures within the static piles. Internal pile temperatures shall be monitored and recorded weekly. Records shall be kept on file at the facility and made available for inspection. An operational plan indicating procedures and schedules for the inspection, monitoring, and restricting of excessive internal temperatures in static piles shall be submitted to the fire code official for review and approval.
    25. Approved material-handling equipment shall be available for moving wood chips, hogged material, wood fines, and raw products during fire-fighting operations.
    1. Exterior storage of finished lumber products shall comply with Permit Holder Guideline #27.

     